2. To adjust the rotor if it is not straight, adjust the height on the underside of the rotor
bar. First unscrew the centre screw.
3. Adjust the height and then retighten the centre screw.
4. For lateral adjustment, loosen the centre screw and then adjust the rotor laterally.
Then retighten the centre screw. If there is a problem with the rotor bearings, contact
your retailer to see if the rotor needs to be replaced.
Loosen the hatch to access the adjustment point.
5. To replace the brush strip around the rotor, remove the existing brush strip by
unscrewing the screws. Install the new brush strip while spinning the rotor by hand.
6. To replace the rotor belt, remove the old rotor belt. Tape down one end of the rotor
belt and then spin the belt so that you can join the two ends together with the supplied
rivet.