34 / 120
Climatix HERU® 400-2400
2018-02-13
Getting started, a few simple steps
Temperature setpoint
The temperature setpoint is selectable as one setpoint value or as two different
setpoints. If only one setpoint is configured, this setpoint will be presented as either
“Setp.
Comf
heating”
or as only
“Setpoint
heating”
with associated dead zones.
If the setpoints for temperature are divided into two types, these will be presented as
comfort and economy with related dead zones. Which of these two setpoint types
HERU® CX uses to regulate is determined in the time switch program or in manual
mode.
•
Setp.comf.heating
This setpoint is usually the one used as
“ma
in
setpoint”.
If the temperature falls
below this value, HERU® CX will switch over to heat regulation to stop the
temperature from falling.
-
Setp.comf.dead zone
The dead zone controls the cooling setpoint according to the formula:
“Setp.comf.heating”
+
“Dead
zone”
= Cooling setpoint
If the temperature rises above the cooling setpoint, HERU® CX will switch
over to cooling regulation to stop the temperature from rising.
A normal dead zone value is 2 °C.
•
Setp.econ.heating
Same principle as comf.heating (see above), but a different setpoint to switch
between in the time switch program.
-
Setp.econ.dead zone
Same principle as comf. dead zone (see above).
Temperature setpoint
Comfort temp.
Economy temp.
Summary of Contents for HERU 400-2400 S
Page 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Page 2: ......
Page 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Page 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Page 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Page 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Page 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Page 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Page 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Page 119: ......
Page 120: ......