50 / 120
Climatix HERU® 400-2400
2018-02-13
External components basic unit
Cooling
Valve actuator and pump for cooling are connected as follows:
48
5
Damper control
cooling
N
PE
230VAC
L
N.B Loop 5-6
Must be mounted
G0
Y
SV2
G
CP2
6
7
8
PE
49
50
For activation/configuration:
Parameter name
Area
Select
Main index > Configuration > Configuration 1
Cooling
No, Water, DX....
Water
Restart
√
, Execute
Execute
Main index > Configuration > Configuration 2
Pump cooling
No / Yes / Yes+exercise
Yes+exercise
Restart
√
, Execute
Execute
Frost protection
If the heating coil is mounted in the HERU® CX unit at delivery, the frost protection
sensor will already be mounted (and connected) on the return line inside the
ventilation unit.
Water heating external, not integrated in HERU® CX
If a water type air heater is used, a frost protection sensor must always be used on the
water’s
return side. If the coil is mounted in a duct, the frost protection sensor with
associated straps and contact paste must be used on the return line pipe.
995010004
Frost protection sensor strap-on temperature detector 2 m with Climatix
mounting kit
Connection of frost protection temperature sensor as follows:
CP2, SV2
Connection
Parameter
GT8
Part no.:
Summary of Contents for HERU 400-2400 S
Page 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Page 2: ......
Page 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Page 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Page 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Page 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Page 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Page 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Page 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Page 119: ......
Page 120: ......