53 / 120
2018-02-13
Climatix HERU® 400-2400
External components basic unit
Connection of filter monitor as follows:
1
2
1
2
2
59
60
Filter monitor
Supply air filter
2 (COM)
1 (NO)
GP3
Filter monitor
Extract air filter
GP4
1
2
2
2 (COM)
1 (NO)
The hoses for pressure measurements are mounted with blue test point connected to
the negative pole (-) on the pressure switch, and red test point connected to the
positive pole (+) on the pressure switch.
For activation/configuration:
Parameter
name
Area
Select
Main index > Configuration > Configuration 1
Filter monitor
No, supply air, Combi, extract
Combi
Restart
√
, Execute
Execute
Filter monitor with display
Filter monitor with display enables active reading of differential pressure over the filter
while retaining the
monitor’s
alarm function. It is sold like regular filter monitors,
supplied separately with a 5-meter connection cable. Activation in Climatix, see Filter
monitor.
Connection
Parameter
Summary of Contents for HERU 400-2400 S
Page 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Page 2: ......
Page 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Page 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Page 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Page 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Page 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Page 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Page 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Page 119: ......
Page 120: ......