62 / 120
Climatix HERU® 400-2400
2018-02-13
External components basic unit
-
Alarm B - HERU® CX operation is not stopped, only information in HMI and the
Alarm B output indicate that something is wrong.
Alarm A can be described as Danger or High alarm class in the HMI.
Alarm B can be described as Low alarm class
Max load is 230 V AC / max 2A
Alarm indication is connected as follows:
33
34
35
36
A-alarm
B-alarm
Signal output for alarm indications can be function-reversed (i.e. changed to NC).
This is done under Unit > Outputs
For more information or assistance, see Climatix Basic Documentation.
AUX operation indication
AUX operation indication is a selectable indication.
The following functions can be selected for indication on the AUX output:
Parameter name Description of indication
Off
Switched off.
Supply/Comf
Comfort mode (Temperature setpoint comfort)
Economy
Economy mode. (Temperature setpoint economy)
Osstp
Not applicable for HERU® CX
Night cooling
Night cooling enabled (in operation)
Support
operation
Support operation; heating and/or cooling enabled (in
operation)
Test Temp
Temperature test enabled for updating of duct sensor
temperature.
Damper exercise Not applicable for HERU® CX
Fire
Fire mode (function dependent on the parameter setting
for fire mode).
Stop
Unit stopped and locked (controller in start phase,
configuration not completed, alarm class danger,
emergency stop).
Cool down
Cool down.
Startup
Unit’s
start routine enabled
Full heat
The heat output signal has reached 100%
Full recovery
The recovery output signal has reached 100%
Full cooling
The cooling signal has reached 100%
Max load on the output is 230 V AC / max 2 A
AUX operation indication is connected as follows:
37
38
Signal output for AUX mode indicators can be function-reversed (i.e. changed to NC).
This is done under Unit > Outputs
For more information or assistance, see Climatix Basic Documentation.
Connection
AUX contact
Indication
Connection
Summary of Contents for HERU 400-2400 S
Page 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Page 2: ......
Page 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Page 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Page 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Page 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Page 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Page 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Page 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Page 119: ......
Page 120: ......