75 / 120
2018-02-13
Climatix HERU® 400-2400
Expansion module with outer components
Air quality sensor CO
2
This function is only used in combination with EXP1.
The system can compensate for fans using the CO
2
sensor GQ1.
Room sensor
Duct sensor
This cannot be combined with room humidity sensors or an external setpoint switch,
as these three functions use the same input.
994020623 CO
2
sensor, room model [LCN-WRF CO2V]
995010012 CO
2
duct model 0
–
2000 ppm, 5 m cable
Connection in EXP1
83
84
85
Air quality / CO2
GND
OUT
GQ1
24V~
3x0,75
For activation/configuration:
Parameter name
Area
Select
Main index > Configuration > Configuration 2
Expansion module
No, One, Two
One
Fan comp. Air
quality
No / Yes
Yes
Restart
Execute
Humidity sensor
This function is only used in combination with EXP1.
The system can fan compensate using humidity sensor GM1.
This is not dehumidification; only fan boost at high humidity levels.
It is possible to use a room humidity sensor or a duct sensor in the extract air. The
sensor is connected to EXP1.
Room sensor
Duct sensor
This cannot be combined with CO2 sensors or an external setpoint switch, as these
three functions use the same input.
GQ1
Part no.:
Connection
Parameter
GM1
Important!
Part no.:
Summary of Contents for HERU 400-2400 S
Page 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Page 2: ......
Page 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Page 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Page 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Page 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Page 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Page 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Page 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Page 119: ......
Page 120: ......