76 / 120
Climatix HERU® 400-2400
2018-02-13
Expansion module with outer components
994020621 Humidity sensor RH, Room sensor [LCN-FW04V]
995010013 Humidity sensor RH, Duct w/ 5 m cable
Connection in EXP1
83
84
85
Humidity sensor
GND
OUT
GM1
24V~
3x0,75
For activation/configuration:
Parameter name
Area
Select
Main index > Configuration > Configuration 1
Expansion module
No, One, Two
One
Room sensor
humidity
No / Yes
Yes
Restart
Execute
Main index > Configuration > Configuration 1
Fan comp. Room
humidity
No / Yes
Yes
Restart
Execute
External setpoint
This function is only used in combination with EXP1.
The system can compensate for temperature setpoints via a room switch.
Compensation is a setpoint effect, i.e. correction -/+ 3K based on the current set value.
Room switch for external setpoint connected to EXP1.
This cannot be combined with CO2 sensors or humidity sensors, as these three
functions use the same input. If external setpoints will be used for effect from BMS,
the signal is connected without the room potentiometer; see connection diagram
below.
994020781 Setpoint switch, Potentiometer Ext.Setp.Temp
Connection
Parameter
TU1
Ext.Setp.Temp.
Part no.:
Summary of Contents for HERU 400-2400 S
Page 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Page 2: ......
Page 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Page 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Page 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Page 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Page 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Page 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Page 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Page 119: ......
Page 120: ......