79 / 120
2018-02-13
Climatix HERU® 400-2400
Miscellaneous
12.
Miscellaneous
Rotary heat exchanger control unit
The rotor is powered by a stepper motor with automatic restart and alarm reset in the
event of power failure. The unit has an integrated blow-off function as standard. When
the rotor is stationary, holding torque is
activated, which ensures that the rotor actually
remains stationary. The control unit is
equipped with a rotation monitor that emits an
alarm if e.g. the belt becomes dislodged. A
built-in input signal offset provides an
efficiency proportional to the input signal.
Two LED lights indicate operation.
The alarm will go off for the following reasons:
•
Rotation monitor
•
Motor temperature
•
Overvoltage
•
Undervoltage
•
Over/under temperature, control unit
•
Short circuit
•
Internal fault
Connection diagram
Varimax