S E R V I C E M E N U : “ F L O W D I R E C T I O N ”
Make settings if the supply air and extract air are connected on the right or left hand.
Press again and then in order to choose
Left
or
Right
.
S E R V I C E M E N U : “ F R E E Z E P R O T E C T I O N ”
(Not used)
Setting of limit value when freeze protection sensor is installed. The sensor (GT5) is installed at the return pipe
on the heating coil. When 3°C higher than set point the valve opens completely. If the temperature continues
to fall to set point the unit will stop, but the valve remains open and the pump output remains active.
Press again and then in order to choose
Limit
: (5°C-10°C).
Press again and then in order to choose ’InOutDiff’
:
(1°C-10°C),
Extract HI:
(19°C-26°C)
and
Extract LO:
(18°C-24°C).
S E R V I C E M E N U : “ S U M M E R C O O L I N G ”
If
”Summer Cooling” ”On”
is chosen, the Summer cooling is activated when the extract air temperature is
higher than ”Extract HI” (19°C-26°C) and outside air is colder than ”Extract - ‘In OutDiff’ (1°C-10°C
difference between the temperature outside and extract air)”.
Summer cooling is deactivated when exhaust air temperature is lower than ”Extract LO” (18°C-24°C)
or when the outside temperature is warmer than ”Extract air - ’InO 1,0ºC’ ”.
If Summer Cooling is activated, water cooling is disabled.
Press again and then in order to choose
On
or
Off
. In order to go forward in “Summer Cooling” press .
Cont.
Cont. next line.
5
5
5
5
Regulation mode
Modbus
Extract
Extract
Extract
Extract
Extract
Extract
Extract
Extract
Modbus
Summer cooling
Sensor calibration
1270411_utg4_HERU_LP_SV_EN.indd 59
2019-03-04 08:16:10
1270411_utg4_HERU_LP_SV_EN.pdf 59
2019-03-04 08:20:50
Summary of Contents for HERU LP
Page 10: ...10 REGLERSCHEMA HERU LP som visar samtliga givare fl desriktning h ger...
Page 32: ...32...
Page 33: ...33...
Page 44: ...44 CONTROL DIAGRAM HERU LP shows all sensors flow direction right...
Page 66: ...66 66...
Page 67: ...67 67...
Page 78: ...78...
Page 79: ...79...