INSTALLATION AND STARTUP
8
OI-6000-X-X-X-X-O OPS_GUIDE_REV 3.1
2.3.1
OPENING THE ENCLOSURE
To prepare the OI-6000 for installation, you must first open the device, exposing the control board and its
components for wiring.
1.
Remove the enclosure lid, unscrewing it from the device enclosure. Set aside.
2.
Gripping the front panel thumbscrews, lift the internal system out of the enclosure and rest it against
the rim of the enclosure opening.
3.
Locate the power cord grip on the top edge of the enclosure.
NOTICE
Disconnecting the sensor connector plug from the sensor housing will allow for the complete removal
of the internal system from the device enclosure. Disconnecting the internal system may provide ease
in accessing the control board terminals for wiring. If this step is performed, it is essential that all
connections are rejoined before returning the internal system back into the enclosure.
2.3.2
CONNECTING POWER
To provide power to the OI-6000, you will need to connect the power cable from the sensor terminal block
on an Otis monitor, or alternate user supplied power source, to the OI-6000 power terminal block located
on the back of the control board. Refer to the following instructions for how to wire your device:
On the GEN II Model OI-6000 Detector:
1.
Feed the power wires through the power hub and into the enclosure.
2.
Locate the power terminal block on the control board and complete the following:
a.
Connect the power (WHITE) wire to the “+12 to +35 VDC” terminal.
b.
Connect the ground (BLACK) wire to the “GND” terminal.
On the Otis Monitor:
1.
Open the enclosure lid.
2.
Using your thumb and forefinger, loosen the front panel thumbscrews that secure the internal system
into the enclosure.
3.
Open the internal system, exposing the internal hardware.
4.
Feed the power wires through a cord grip and into the enclosure.