PRODUCT SETTINGS AND CONFIGURATION
OI-6000-X-X-X-X-O OPS_GUIDE_REV 3.1
25
3
PRODUCT SETTINGS AND CONFIGURATION
The product settings and configuration menu allows the end-user to tailor the device settings to meet their required
specifications and/or site conditions.
The product settings and configuration menu consist of the following screens:
Relay Test
Network ID
System Information
Null/Calibration Timers
Unit Info
Background Setting
Relay 1: Latching/Non-Latching Setting
Relay 2: Latching/Non-Latching Setting
Relay 1: Fail-Safe Setting
Relay 2: Fail-Safe Setting
Calibration Method
RS-485 Modbus Address Setting
RS-485 Modbus Baud Setting
4-20 mA Offset Settings
o
Zero Offset Setting
o
Full-Scale Offset Setting
Display Screen Contrast Setting
Return to Factory Default Settings
While the device is in normal operating mode, press and hold the MENU button, for approximately 6 seconds, until the
product settings and configuration menu is activated and open on the display screen.
3.1
RELAY TEST
The relay test simulates a gas level reading, indicating the presence of a toxic gas at the sensor. The relay test is
used to ensure the proper functionality of the relay settings on the monitor. The test can also be used to simulate
emergency/safety drills onsite.
NOTICE
The triggering of relays from the detector will also simulate low and high level alarm relays at the monitor. Monitors
cannot distinguish between real and simulated data received. When the monitor relays are triggered, alarming
devices will perform as intended, initiating emergency procedures as if a harmful or toxic gas was actually present.
To prevent this from occurring, set the monitor to calibration mode before performing the relay test. Calibration
mode of the monitor will allow the transmission of the data, without the activation of the monitor relays. Consult
the Sensor Calibration section of this manual for instructions on how to perform this procedure.
It is recommended that a relay test be conducted EVERY 30 days, alongside the maintenance and calibration of the
detector.