PRODUCT SETTINGS AND CONFIGURATION
26
OI-6000-X-X-X-X-O OPS_GUIDE_REV 3.1
3.1.1
PERFORMING THE RELAY TEST
The relay test gas level reading can be increased or decreased in increments of 5% of the sensor scale,
up to 100% of the sensor scale.
1.
Press the ADD button until the low and high alarm levels are reached and the relay(s) are triggered
to light all visual alarm(s) and sound all audio alarm(s) on the monitor.
2.
Once all relays have been tested and the test is complete, press the SUB button to return the relay
test reading back to zero and to deactivate the monitor alarm(s).
3.
Press the MENU button to advance to the System Information screen.
3.2
NETWORK ID
The Network ID is used to synchronize the communication between the Otis Monitor and Sensor Assembly:
There are 52 networks available with the GEN II 900 MHz radio.
There are 78 networks available with the GEN II 2.4 GHz radio.
The monitor and sensor assembly must have the same Network ID in order to communicate.
1.
Press the ADD or SUB button until the Network ID matches the value being used on the Primary
Monitor.
2.
Press the MENU button to advance to the System Information screen.
NOTICE
This page will not appear if no radio module is installed. Please skip to section 3.3 SYSTEM INFORMATION.
Summary of Contents for GEN II OI-6000
Page 1: ......
Page 2: ......
Page 4: ......
Page 28: ...INSTALLATION AND STARTUP 22 OI 6000 X X X X O OPS_GUIDE_REV 3 1...