PRODUCT SETTINGS AND CONFIGURATION
OI-6000-X-X-X-X-O OPS_GUIDE_REV 3.1
37
3.14
RETURN TO FACTORY DEFAULT SETTINGS
Returning the OI-6000 to its factory default settings will reset all customization of the device, including the null and
calibration settings of the sensor element.
OI-6000 Product and Configuration Factory Default Settings
Configuration
Setting
Relay Test
--
Network ID
5
System Information
--
Null/Calibration Timer
*Cleared*
Unit Information
--
Background Setting
4
Relay 1: Latching/Non-Latching
UnLatch
Relay 2: Latching/Non-Latching
UnLatch
Relay 1: Fail-Safe Setting
No (Off)
Relay 2: Fail-Safe Setting
No (Off)
Calibration Method
Manual
RS-485 Modbus Address Setting
1
RS-485 Modbus Baud Setting
9600 bps
4-20 mA Zero Offset Setting
4.00 mA
4-20 mA Full-Scale Offset Setting
20.00 mA
Contrast
--
OI-6000 Operation Factory Default Settings
Configuration
Setting
Sensor Element Null
*Cleared*
Sensor Element Calibration
*Cleared*
Sensor Assembly Low Alarm Setting
10% of Sensor Scale
Sensor Assembly Low Alarm Rise/Fall Setting Rise
Sensor Assembly High Alarm Setting
15% of Sensor Scale
Sensor Assembly High Alarm Rise/Fall Setting Rise