The signal wire of each unit is run to the signal terminal of the neighboring sensor. With each device connected to the previous
device via the signal wire, a “chain” is created, with the first device in the chain directly connected to the monitor.
RS-485 Modbus Connection Distances for Electrical Wiring
Distance
Length
Gauge Size
Twisted Pairs
Short
< 100 Feet
22 to 24 Gauge
Shielded, in areas of high noise
Medium
101 Feet to 1,000 Feet
18 to 20 Gauge
Shielded, in areas of high noise
Long*
1,000 Feet to 4,000 Feet
18 to 20 Gauge
Shielded, in areas of high noise
(*) Terminating resistor may be required for the last device in the daisy-chain.