APPENDICES
OI-6000-X-X-X-X-O OPS_GUIDE_REV 3.1
59
OI-6000 MODBUS REGISTER MAP ENUMERATION KEYS
Register Address 4: Gas Type
Response
Gas Type
0
H2S – Hydrogen Sulfide
1
SO2 – Sulfur Dioxide
2
O2 – Oxygen
3
CO – Carbon Monoxide
4
CL2 – Chlorine
5
CO2 – Carbon Dioxide
6
LEL – Combustible Gas
7
VOC – Volatile Organic Compounds
9
HCL – Hydrogen Chloride
10
NH3 – Ammonia
11
H2 – Hydrogen
12
CLO2 – Chlorine Dioxide
13
HCN – Hydrogen Cyanide
17
NO2 – Nitrogen Dioxide
26
PH3 -- Phosphine
Register Address 5: Unit Type
Response Unit Type
0
PPM
1
%
Register Address 8: Mode of Sensor
Response
Sensor Mode
0
Normal Operating Mode
1
Null Mode
2
Calibration Mode
3
Relay Test Mode
5
Diagnostic Mode
6
Advanced Mode
7
Administrator Mode
Register Address B/11: Fault Code
Response
Fault Type
0
No Fault
1
Loss of Communication with Sensor Board
4
Loss of Communication with Sensor Element/Housing
5
Null Error
6
Calibration Error
Summary of Contents for GEN II OI-6000