PRODUCT SETTINGS AND CONFIGURATION
25
OI-6000K-X-X-X-NXP-X OPS_GUIDE_REV 1.0
3.5
LATCHING AND NON-LATCHING RELAY SETTINGS
Relay 1 and Relay 2 can be set to latching or non-latching. Relays set to non-latching will automatically
deactivate when the detected gas level falls below the corresponding alarm setting. Conversely, latching
relays, once activated,
MUST
be manually reset at the device, regardless of the change in gas detection level
readings.
The factory default settings on the OI-6000K for Relay 1 and Relay 2 are non-latching. During installation
and setup, Relay 1 and Relay 2 are commonly customized as the following:
Common Relay 1 and Relay 2 Settings
Relay
Alarm Setting
Latching/Non-Latching
Relay 1
Low
Non-Latching
Relay 2
High
Latching
3.5.1
RELAY 1: LATCHING/NON-LATCHING SETTING
1.
Use the
ADD
and
SUB
buttons to toggle between the “UnLatch” and “Latch” options.
2.
Press the
MENU
button to select the desired setting and to advance to the Relay 2
latching/non-latching setting screen.
NOTICE
For non-latching alarms, the alarms will
NOT
deactivate until the gas level reading at the
sensor has fallen 10% below the alarm set-point.
For latching alarms, the gas level reading
MUST
be below the alarm set-point before the
alarm can be deactivated.