OUMAN EH-203
FOR STARTERS
OUMAN EH-203
Ouman EH-203 is a multifunctional heating controller which is
adaptable to many different types of heating systems. Ouman EH-203
has the ability to control two heating circuits and one hot water
control circuit simultaneously. Your controller's display changes
depending on the connections and selected functions that are in use.
All the different functions are presented in this user manual. In the
beginning we present the basic principles for using the controller.
User panel
Regulator opens the 3-point
controlled actuator.
Regulator closes the 3-point
controlled actuator.
Height up the pillar shows
the position of the voltage
controlled actuator.
Valve is fully open (100%)
and the control voltage is 10 V.
Valve is fully closed (0%) and
the
control voltage is 0 V or
2 V (2 ... 10 V actuator).
Decrease
button
INFO
-button -gives
operating instructions and
additional information on
the display in different
situations.
ESC
press to
return to the
previous display
HINT!
When you press + button in adjoining basic display mode, the
regulator displays all the measure-ment results in turn and then
returns to the basic display mode.
Symbols which indicate
actuator control mode.
Increase -
button
OK
button
H1 Automatic
Outdoor
-15°C
SupplyTemp52°C
>Selection
Regulating circuit code
Browse button
Group select button
indicates the regulating circuit
in question (heating circuit H1
shown here).
- moves the
> cursor up and down.
-
moves you from one
regulating to the next.
The regulating circuits are:
H1, heating regulating circuit,
H2, heating regulating circuit and
HW, domestic hot water
regulating circuit.
Remote control options:
Most of EH-203's user level functions can also be
carried out via GSM phone text messages.
Remote control via a GSM phone
Text message use is illustrated on page 20.
Web based user interface
Ouman controllers can also be controlled and monitored
via an inexpensive web user interface. A web scanner is
easy to use and can illustrate remote control and
monitoring of even large Ouman control systems
regardless of the time and place.
KEYWORDS:
Measurements/
Heating curves/
Relays/
H1 Settings/
H2 Settings/
DHW Settings/
H1 Operat.mode/
H2 Operat.mode
H1 Info water
H2 Info water
Measurements
H1 Supply=52/
H1 Room=21.2/
H1 Ret.water=28/
Outdoor=-15/
H2 Supply=48/
H1 Settings
Room temp.=21.5/
Temp drop(w)=0/
Min. limit=15/
Max. limit= 70/
Room compens.=4/
Pre-increase=0/
Autumn dry=2/
H1 Curve:
(-20=58;
0=41;
+20=19)
H1 Operat.modes:
*Automatic/
Nominal oper./
Reduced oper./
Manual electr.
open=000%/
Manual electr.
closed=000%/
Valve flushing/