Measurement information:
Strip
con-
nector
OUMAN EH-203
MITTAUKSET
OUMAN EH-203
OUMAN EH-203
MEASUREMENTS
OUMAN EH-203
Additional information
Putting sensor into use and removing it from use:
If the outdoor sensor is not connected, the regulator assumes that the outdoor temperature is
0°C and a sensor fault message appears on the display (Outdoor temp err). When the outdoor
sensor is connected, the regulator automatically takes it into use.
(See page 17)
After adding other sensors
you must go to start function!
Resistance
value table
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
90
100
110
177 100
130 400
96 890
72 830
55 340
42 340
32 660
25 400
19 900
15 710
12 490
10 000
8 064
6 531
5 330
4 368
3 602
2 987
2 490
2 084
1 753
1 482
1 259
917
680
511
Measure-
ment:
Setting
range:
Attention!
°C
9
INSTRUCTIONS FOR CONNECTING SENSORS:
TMR
Free temp. measurement
(Meas. 11)
34
5
6
78
9
10
11
2 x 0.8
2 x 0.8
2 x 0.8
2 x 0.8
2 x 0.8
2 x 0.8
2 x 0.8
2 x 0.8
TMW or TMS
TMW or TMS
TMW or TMS
TMW or TMS
TMW or TMS
TMW or TMS
TMW or TMS
Meas.3
Meas.4
Meas.5
Meas.6
Meas.7
Meas.8
Meas.9
Meas.10
Meas.11
Meas.1
TMO
TMW or TMS
T1
1
T
1
1
1
2
2 x 0.8
2 x 0.8
2 x 0.8
Meas.2
Outdoor temp. sensor
H1 Supply water sensor
H1 Room sensor
H1 Return water sensor
H2 Supply water sensor
Free temp. measurement
(Cold water)
HW supply water sensor
HW circulating water sensor
(anticipate -sensor)
Free temp.measurement
(
)
DH ReturnHE3
Free temp. measurement
(
)
DH ReturnHE2
1
Free measurement; name using the text editor
r position in regulating circuit HW
11
(m )
ActuatorHW
Actuato
Out temp
2
H1 Supply
Supply
3
H1 Room
4
H1 Ret.water
Return
5
H2 Supply
Supply
6
Cold water
H2 Room
6
Wind
6
7
HW supply
HW (d
8
HW circul.wat
9
H2 Return
10
Free temperature measurement that can be
labelled or a measurement that controls the burner
and/or heating resistor.
DH m3
Inst. l/s
DH Mwh
Inst. KW
Wat m3
ActuatorH1
Actuator
ActuatorH2
Actuator
Outdoor temperature
water temperature in regulating circuit H1
Room temp. in regulating circuit H1 (room comp.)
water temperature in regulating circuit H1
water temperature in regulating circuit H2
Free measurement; name using the text editor
6
Room temp. in regulating circuit H2 (room comp.)
Wind speed (% of sensor's range)
omestic hot water) supply water temp.
Temp. of HW return water in heat exchanger.
(an anticip. sensor is used in the HW heat
exchanger to improve the setting results)
Free measurement; name using the text editor
Measured consumption of DH water
Momentary district heating water consumption (l/s)
Measured energy consump. of DH water (MWh)
DH energy consumption in kW (5 min. period)
Measured water consumption of facility (m )
position in regulating circuit H1
position in regulating circuit H2
3
3
Network pressure: Pressure in the heating network
DH ReturnHE3
DH ReturnHE2
T1
T2
T3
T4
T5
T6
T7
T8
T9
T10
T1
1
TMW or TMS
Interchangeable (p. 30). If
several compens. are needed,
the data must be read through
the net and the wind is m/s
and the light is lux (p. 36).
Can be read through the net
-50...+50
0 . . . + 1 3 0
-10...+80
0 . . . + 1 3 0
0 . . . + 1 3 0
-10...+80
0 . . . + 1 3 0
-10...+80
0 . . . + 1 3 0
0 . . . + 1 3 0
0 . . . + 1 3 0
0...+120
0...99999,9
0...99999,9
0...3276,7
0...99999,9
Can be read through the net
Consumption data can be
read as digital inputs or
through the net.
Appears only when using a
0...10V (2...10V) controlled
actuator.
Relay 1 controls the burner a
nd relay 2 controls the
heating resistor.