OUMAN EH-203
ACTUATOR SELECTION
OUMAN EH-203
Press the
button to move the cursor to the actuator control mode that
you want to use. Press
OK.
+
OK.
-
3-point control with a driving time of 150 s is a factory setting in H1 and H2
control circuits and 0…10V control with a driving time of 15 s is a factory
setting in the DH control circuit. 230V 3-point control can be selected after
the relays have first been reserved for 230V actuator control. After you select
the actuator control mode the controller requests the actuator driving time.
The running time indicates how many seconds go by if the actuator drives
a valve nonstop from a closed position to an open position.
Press the
or
button to set the time. Press
The
character indicates which control mode is being used.
The
button moves you from one regulating circuit to the next.
Directions for entering the
maintenance mode are on page 21
The control mode for each regulating circuit actuator is selected in
actuator selection. Options are either 24 VAC 3-point control or DC
voltage control (0...10V or 2...10V). If relays 1 and 2 are free, they can be
utilized to implement one 230VAC 3-point control. (first choose "230V
Actuator" for the relay control mode. See pages 26 and 27)
H1
3-p./time
s
0-10V
2-10V
3-p230V
s
Actuator sel
15
150
0
VALVE ACTUATOR CONNECTION:
Open
Closed
51
53
55
57
59
61
3-point 24 VAC
3-point controlled
actuator (24VAC)
0...10V or 2...10V DC controlled
actuator (24VAC)
3-point controlled actuator
(230 VAC)
Regulating circuit H1 actuator's control output is M1.
Regulating circuit H2 actuator's control output is M2.
Regulating circuit HW actuator's control output is M3.
Attention!
If "230V actuator" has been
selected for relays 1 and 2, one 230VAC 3-
point controlled actuator can be connected to
the regulator for any regulating circuit (H1, H2
or HW). Selection of relay control modes is
shown on pages 26 and 27.
H1 actuator
(control output M1)
52
54
56
58
60
62
H1 Maint mode
Tuning values
Settings
Trends
Actuator select
Relay1 control
71
72
73
74
75
Open
Closed
L
Actuator 230 VAC 3-point
Press the
button to move the cursor to “Actuator select”. Press
OK
.
H2 actuator
(control output M2)
HW actuator
(control output M3)
Open
Closed
3-point 24 VAC
Open
Closed
3-point 24 VAC
24
VAC
0-10V
or
2-10V
51
53
55
57
59
61
24
VAC
0-10V
or
2-10V
24
VAC
0-10V
or
2-10V
52
54
56
58
60
62
24
VAC
H1 actuator
(control output M1)
H2 actuator
(control output M2)
HW actuator
(control output M3)
Ouman M31C150
Ouman M41A15
25