1. The regulator restores factory settings to the charasteristic
heating curve settings.
2. Eliminates clock functions
3. Restores user and maintenance level settings
4. Selects automatic control for the operating mode
5. Selects the basic regulator for the regulator type.
6. Identifies the connected sensors and assumes which regulating circuits
are in use.
7. Restores factory settings to the tuning values and trend sampling intervals.
8.
lay controls are not in use.
10. Sets alarm Dig 1 (Dig 2, Dig 3) as an assumption into digital inputs.
11.
12. Erases the telephone number and restores the factory settings to the
modem settings.
Original factory settings can be restored with the regulator in the following
manner:
Selects 0…10V for actuator control with a running time of 150 s in H1 and
H2 and the 3-point control for actuator control with a running time of 15 s
in the hot water circuit.
9. Re
Measurements are not read from the energy meter or bus.
Press the
button to move the cursor to "Special mainten.
The cursor is at "Rstore settings". Press
”.
Press
OK.
OK.
Directions for entering the
maintenance mode are on page 21.
Restore original factory settings:
ORIGINAL FACTORY SETTINGS:
21.5 °C
0 °C
15 °C
70 °C
0 °C
4.0 °C
0 °C
0 °C
0 °C
2 °C
70°
50°
19 °C
55°C
55.0°C
User level settings:
Room temperature
Temperature drop (supply water)
Min. allowed supply water
Max. allowed supply water
Parallel shift
Room compensation ratio
Wind compensation ratio
Sun compensation ratio
Pre-increase
Autumn drying
Burner ON
El.Heater ON
Valve close
Relay 1 temperature limit
Domestic hot water
Characteristic heating curve:
80
65
50
35
20
20 0 -20 °C
H1 Curve:
0 = 41°C
+
-20 = 58°C
20 = 18°C
Start function:
2 h/ 0 h
0 h/ 0 h
70 °C
0 °C
Maintenance level settings:
Outdoor temp. delay H1/ H2
Pre-increase H1/ H2
Domestic hot water alarm
Domestic hot water increase
Factory setting:
Relays:
80
65
50
35
20
20 0 -20 °C
H2 Curve:
0 = 42°C
+
-20 = 62°C
20 = 20°C
Operating mode:
Actuator selection:
Tuning values:
H1, H2
0.5h
70°C
5°C
15°C
10°C
10°C
30°C
30°C
75°C
60min
999kW
99.9l/s
6°C
120s
-15°C
Special maintenance settings:
Room temperature delay
Return water maximum H1
Return water min. at 0°C
H1 Supply water min at 0°C
Output limit
½ exhaust
Domestic hot water alarm delay
Relay 1 outdoor temperature limit
Return water min at -20 °C
H2 Supply water min at 0°C
H1 Supply water min at -20°C
H2 Supply water min at -20°C
The amount of deviation from the
setting, which causes the alarm
H1/H2/HW/R1
The duration of the deviation that
causes the alarm
Water flow limiting function
OUMAN EH-203
RESTORING SETTING
OUMAN EH-203
Restore original
Factory settings
No
Yes
H1 Control modes
Automatic ctrl
Nominal oper.
Reduced oper.
Stand-by
Manual mech.
Manual electr.
Special mainten.
Rstore settings
Settings
Meas. 6 setting
Dig1 selection
Dig2 selection
Dig3 selection
Enrgy meter
LON initaliz
Net measurement
TextMessageSett.
Curve type
Regul.Circ.Name
H1
3-p./time 150s
0-10V
2-10V
3-p 230V
Actuator sel
Start function
H1 Basic regul
H1 Self-learn
H1 Not in use
H2 Basic regul
H2 Self-learn
H2 Not in use
HW Regulator
HW not in use
HW Tuning values
P-area:
70°C
I-time:
18s
D-time:
0.0s
Anticipate:140°C
Quick run:
60%
H1 Tuning values
P-area:
140°C
I-time:
50s
D-time:
0.0s
Relay1 ctrl sel
Not in use
Heat.pump
Time program
Time/Outdr tmp
230V actuator
Temp operated
Burner control
Relay2 ctrl sel
Not in use
Pump
Time program
230V actuator
El.Heater ctrl
Press the
button to move the cursor to "Yes
”.
Press
OK.
HW Control modes
Automatic ctrl
No temp. incr
Contin.incr.
Manual mech.
Manual electr.
28
Restoring settings:
HW
3-p.
0-10V
2-10V
3-p 230V
Actuator sel
./time 15s
HW