Factory
settings:
Press the
button to move the cursor to ”Settings". Press
OK
.
Explanation:
The average inside temperature measurement time
which the room compensation uses.
Return water maximum allowed temperature at which
the regulator begins lowering the return water temp.
Freeze protect limit. Minimum return water temperature
when the outdoor temperature is 0°C.
Maximum district heating output at which output limiting
begins in regulating circuit H1.
Drop in supply water temperature when the exhaust fan
is at ½ speed (see page 32).
The length of time from which the regulator calculates
the HW average temperature for the alarm.
The outdoor temperature limit for relay 1 (in use when
time /outdoor temperature control has been selected for
relay 1's control mode)
Freeze protect limit. Minimum return water temperature
when the outdoor temperature is -20°C.
Lower limit of supply water during a free temperature
drop in the regulating circuits H1/H2 when the outdoor
temperature is 0°C. (stand-by function)
Lower limit of supply water during a free temperature
drop in the regulating circuits H1/H2 when the outdoor
temperature is -20°C. (stand-by function)
Maximum district heating water flow at which output
limiting begins in regulating circuit H1
H1/H2/HW supply water temperature deviation from the
setting determined by the regulator which causes the
alarm
Temp. (meas. 11) deviation from the setting of "R1 Temp
operated" which causes the alarm. This setting appears
if "Temp operated" has been selected in the relay1
control mode (see page 26).
The alarm goes off if the deviation has lasted for the set
time.
Range:
0...2
25...95
5...20
10...50
5...20
5...20
10...50
10...50
1...75
1...75
1...75
1...75
0...90
0...999
0.1...99.9
0...-10
0...30
-30...+20
INFORMATION ABOUT SPECIAL MAINTENANCE SETTINGS:
Directions for entering the
maintenance mode are on page 21.
0.5h
70°C
5°C
15°C
10°C
10°C
30°C
30°C
75°C
75°C
75°C
75°C
60 min
999 kW
99.9 l/s
-6°C
30s
-15°C
Settings:
Attention!
Only L1
Only L1
Only L1
Only L1
Only L1
Only L1
OUMAN EH-203
ERIKOISHUOLTO
Asetusarvot
OUMAN EH-203
OUMAN EH-203
SETTINGS
OUMAN EH-203
Settings
Ret.min (0)
Ret.min (-20)
H1SuppMin(0)
H1SupMin(-20)
H2SupMin (0)
H2SupMin(-20)
H1 Dev.alarm
DevAlaDela
min
Output lim
kW
WaterLim
l/s
1/2exhst
°C
HW alrm dela
s
R1 Outd.
°C
Room delay
h
RetWat.max
°C
H2 Dev.alarm
HW Dev.alarm
R1 DevAlaM11
0.5
5
70
75
75
75
75
60
99,9
15
10
30
10
30
999
-6
30
-15
Special mainten.
Rstore settings
Settings
Meas. 6 setting
Room delay
RetWat. max
Ret.min (0°C)
Ret.min(-20°C)
H1 SuppMin (0°C)
H2 SuppMin (0°C)
H1 SupMin(-20°C)
H2 SupMin(-20°C)
½ exhst
HW alrm dela
R1 Outd.
H1 Dev. alarm
H2 Dev. alarm
HW Dev. alarm
R1 DevAlaM11
DevAlaDela
Output lim
WaterLim
In the Ouman EH-203 heating regulator the user can adjust
most of the settings (see settings p. 6-7). Some of the settings that control
the regulator's functions can be set in the maintenance mode (see page 23)
and some in special maintenance. Seldom needed settings can be
adjusted in special maintenance.
Press the
button to move the cursor to the parameter that you want
to change. Press
Press the
or
button to change the setting. Press
OK
OK
.
.
-
+
29