OUMAN EH-203
MEASUREMENT 6 SETTING
OUMAN EH-203
Directions for entering the
maintenance mode are on page 21.
Erikoishuolto
Aset.palautus
Asetusarvot
Mitt. asetukset
Meas. 6 setting
Cold water
H2 Room temp
Wind meas.
Sun meas.
Not connected
Comp/Meas. data
Min /
0%
Max / 100%
Labeling measurement 6 using the text editor:
The factory setting for measurement 6 is "Cold water".
Relabeling is shown on page 8.
Press
Press the or
button to set a limit and
press
to confirm.
OK
.
-
+
OK
The
character indicates which measurement has been chosen for
measurement 6.
Selecting measurement 6:
Setting limits for the wind sensor measurement message:
Setting the limit for the wind sensor measurement message.
You must set compensation area limits in volts. The minimum limit
indicates where in the emitter's measurement area compensation
begins and the maximum indicates at which measurement area the
compensation is at a maximum level. (To set the amount of
compensation see p. 6)
Name change
Cold water
Give new label
Special mainten.
Rstore settings
Settings
Meas. 6 setting
Dig1 selection
Measurement 6 can be used as a free temperature measurement,
Room temperature measurement, wind measurement or measurement of
the pressure in the heating or ventilation network. It is factory set as a free
temperature measurement labelled “Cold water”. The label for
Measurement 6 can be changed using the text editor.
0…10V transmitters are used in wind-/pressure measurements. In this
mode you can set the wind transmitter area that wind compensation occurs
at. The wind compensation temperature amount is set in Settings (see p.6).
A pressure transmitter can be used to set alarm limits for upper limit, fill,
and lower limit alarms.
Press the
button to move the cursor to what you want to connect to
measurement 6. Press
OK
.
Press the
button to move the cursor to "Meas. 6 setting". Press
OK
.
30
E.g., the effect of wind compensation on supply water
A wind sensor is in use which has a measurement area of 0… 20m/s. You
want wind compensation to begin when the wind velocity is 6 m/s and
compensation to be at maximum value when the wind velocity is 14 m/s.
Wind compensation is set at 4°C (setting range -7 …7°C).
See the next page for instructions on setting the measurement area for the
network pressure and setting pressure alarms.
Network pressure
:
Supply water temperature
Wind compensation
°C
7
5
3
2
1
0
6
4
wind comp. setting
0
Min/30%
Max/70%
Measurement message
0 1 2
4 5
6
8
9 10 V
3
7
measurement message sent by wind transmitter
0
100%
30%
70%
percentage of transmitter's measurement area
20 m/s
18
16
14
12
10
8
6
4
2
0
wind comp.
begins
wind velocity
The wind transmitter is connected in the same way as the pressure
transmitter using a voltage divider resistor (see next page, connection 1)
wind comp. at
a maximum level