OUMAN EH-203
BUS CONNECTIONS/ LON initialization
OUMAN EH-203
LON initializ.
No
Yes (Service
switch)
Eg. LONAK 2x1,3 mm
2
Press the
button to move the cursor to
. Press
"Yes
(Service switch)"
OK
.
35
T
he Ouman EH-203 controller can be connected to the
MODBUS, RS-485 or LON bus. When the EH-203 controller is connected
to the bus, a (Modbus-200, EH-485, or LON-200 card) bus adapter card
(optional equipment) is installed. Detailed instructions for installing and
initializing the bus adapter card are provided.
When connecting the controller to the LON-field bus, LON-bus
initialization occurs in the controller's special maintenance mode.
Other buses do not have to be initialized from the controller.
LON-initializ.
No
Yes (Service
switch)
When using an LON bus connect the protective
ground of the 230VAC supply current to strip
connector 81 of the controller!
LON-net
(78kbp
s)
AC
EH-485-adapter card
LON-200
adapter card
Eg. Datajamak
2x(2+1)x0.24
AB
C
RS-485-net
EH-203
EH-203
Modbus-net
MODBUS-200-adapter card
Eg.. LONAK 2x1,3 mm
2
AC
EH-203
Connect the EH-203 to a MODBUS field bus:
LON initialization:
In this special maintenance mode you can
control the Neuron processor's service pin
which is on the LON-200 card so that the
Neuron sends the bus its own identification (48
bit Neuron ID). This procedure is necessary
when initializing EH-203 + LON-200 into the
facility's LON net
.
Directions for entering the
maintenance mode are on page 21.
Special mainten.
Rstore settings
Settings
Meas. 6 setting
Dig1 selection
Dig2 selection
Dig3 selection
Enrgy meter
LON initaliz
Net measurement
Curve type
Regul.Circ.Name
Press the
button to move the cursor to
.
Press
"LON initializ.”
OK
.
Connect the EH-203 to a RS-485 field bus:
Connect the EH-203 to a LON field bus: