Last Update: 2011-June INSTRUCTION MANUAL FOR THERMOSYPHONIC SYSTEMS
27/35
©TANSUG MAKİNA LTD. 2008
6.3.3
Proceed to fill the rest of the system with water. Take into account that the
maximum fluid capacity of the secondary circuit is approximately 10lt. (If the system is to be
put in an area risk free of frost, this filling can be made entirely with water).
6.3.4
Install the security valve. When the fluid in primary circuit reaches high
temperature, its pressure will raise as well. When this pressure exceeds 3 bar, the security
valve will open and some of the heat transfer fluid will be disposed through the valve. This
process will happen several times until finally when there is enough air in the upper part of
the jacket. After that, this space in the jacket will serve as an “expansion tank” and the
security valve will not work again.
6.3.5
Make sure there’s no leakage in the connections and repeat such test once
temperature, therefore pressure, rises.
6.
ELECTRICAL ELEMENT
6.1
Your thermosyphonic system can be incorporated with an optional electrical heater of
2000 W, to be used as an auxiliary heating system during low irradiation or high consumption
seasons. (Remember that in some European markets auxiliary system is not allowed).
6.2
To connect the resistance to electrical net, the directives marked by the Low Tension
ElectroTechnical Regulation must be followed. For that, it is essential to use a three thread hose
with 2.5 mm section and it must be assured that proper grounding is established.
MODEL
P 101
P 121 P 151
P 191 P 192 P242 P 302
Close Loop Volume (lt.)
9,00 12,00
13,00 14,00 15,00 20,00 21,00
Temperature
ºC
%
-5
AFLUS
1,35 lt
1,80
1,95
2,10
2,25
3,00
3,15
WATER
7,65 lt 10,20
10,20 11,90 12,75 17,00 17,85
-9
AFLUS
1,80 lt
2,40
2,40
2,80
3,00
4,00
4,20
WATER
7,20 lt
9,60
9,60 11,20 12,00 16,00 16,80
-13
AFLUS
2,25 lt
3,00
3,00
3,50
3,75
5,00
5,25
WATER
6,75 lt
9,00
9,00 10,50 11,25 15,00 15,75
-17*
AFLUS
2,70 lt
6,60
3,60
4,20
4,50
6,00
6,30
WATER
6,30 lt
8,40
8,40
9,80 10,50 14,00 14,70