Last Update: 2011-June INSTRUCTION MANUAL FOR THERMOSYPHONIC SYSTEMS
31/35
©TANSUG MAKİNA LTD. 2008
CHAPTER II
INSTRUCTIONS FOR THE USER
WARNING
: Make sure that all installation is carried out by your authorized installer. Check all
valves are properly working and the system is completely filled with water and antifreeze fluid.
In case of failure, read the instructions at the troubleshooting section. Always call your
authorized service store before taking any action.
12. SAFETY & SECURITY COMPONENTS
Your system has two circuits, each secured by a number of safety and security components.
The system comes equipped with safety components for the primary circuit. All safety
components required for the secondary circuit must also installed by your authorized installer.
12.1 Primary Circuit (Closed Loop Line):
•
Expansion tank:
preset 1,5 bar, working pressure 4 bar
•
Pressure relief valve:
5 bar
•
Air vent
160° C
12.2 Secondary Circuit (Cold Water Line):
•
Pressure reducer :
preset to 3 bars
•
Non-return valve
•
Pressure relief valve
5 bars
•
Control Valve
13. MAINTENANCE
The following table lists the key components of your system that require regular inspection
and maintenance.
INSPECTION
Correct Status
Period of Control Average Life
Mg Anode
Must be complete
Annually
2 years
Antifreeze Fluid
Must be full
Annually
1 year
Pipe Insulation
Must be intact and solid
Annually
3 years
Fittings Accessories
Must function properly & not leak
Annually
2 - 5 years
Panels
(Closed Loop)
Inside panel must remain completely water and
weather proof
Every 2 years
12-20 years
Boiler –
closed circuit
No leakage and corrosion should occur in the tank
Annually
8-10
years