There are two screw terminals for each relay contact. Each
can handle up to 8 amps. They are tied together internally.
COM 11 and COM 21 are the common relay connections.
Either can be used for loads under 8 amps. If the load
exceeds 8 amps, use both COM 11 and COM 21.
r
NO 14 and NO 24 are normally open relay connections.
Use both 14 and 24 terminals for loads exceeding 8 amps.
r
NC 12 and NC 22 are normally closed relay connections.
Use both 12 and 22 terminals for more than 8 amps.
NOTE:
If a load exceeds 8 amps, use both screw terminals for any
given relay contact to distribute the current and avoid overloading
the screw terminal.
Terminal screw torque – 0.5 Nm (4.4 inch lbs)
12V RELAY
C
OIL
NO
NC
COM
INVERTER
ON/OFF
AUX +
AUX -
XCT -
XCT +
TWO WIRE START
GENERATOR
HOOK UP
GENERATOR
FX INVERTER/CHARGER