background image

Worldwide Corporate Offices

North America

 

Tel: +1 360.435.6030 
Fax: +1 360.435.6019

Europe

 

Tel: +49 9122.79889.0 
Fax: +49 9122.79889.21

Latin America

 

Tel: +1 561.792.9651 
Fax: +1 561.792.7157

Asia Pacific

 

Tel: +852 2736.8663 
Fax: +852 2199.7988

p/n 044-026-B0-001, Rev. A (03/2015)

Figure 12, Breaker and Busbar Locations

Positive Busbar with 

Transparent Cover

Negative Busbar

Load Cables

Main Breaker

String 1 Breaker

String 2 Breaker

String 3 Breaker

Battery Installation

Figure 11, Battery Wiring / Bus Connections Stackup

Figure 10, Battery Positive and 

Negative Positioning/Wiring

7.  Using the positive battery cable located at the top 

of the enclosure, wire the cable to the rightmost 

positive battery terminal on the top of the shelf of 

the enclosure.

8.  Apply corrosion inhibitor to the terminals and 

connections.

9.  Re-install the securing bar using the 8 screws 

removed in step 2.

10. Repeat steps 2-7 for the middle and bottom shelf, 

respectively.

11. Feed the load cables  through the bottom of the 

enclosure's rubber grommet. An LB with a 2" (5.1 cm) 

conduit may be connected to any of the knockouts 

on the riser if required.

12. Connect the positive load cable to the busbar on 

the right of the enclosure wall and the negative load 

cable to the busbar on the left of the enclosure wall 

(See Figure 12).

13. Installation is complete. Activate the breakers per 

installation needs.

Battery Installation

3/4" x 1/4-20 Bolt

Split Washer
Flat Washer
Battery Cable

Battery Terminal

Busbar

Battery Interconnect

Battery Cable Wiring

Top-Down View