E-023-2-E
2
③
Select the output levels to set from the drop-down lists by clicking the triangles on the right side of the
"Analog" and "Pulse" items, as shown in Fig. 43 and Fig. 44.
④
Output levels are as follows:
Note: The "Error output" functions when there is a "Sensor Failure", "Xmtr Failure", or "Parameter
Alarm". For a description of error items, refer to section 3.11.4 "Error and status display list".
⑤
Once all the settings are complete, click the "OK" button to display the message box (Fig. 45).
Click "OK" here to change the settings to the inputted values, and to reflect the changed setting values
in the flowmeter
’
s output. For the sake of safety, if the flowmeter
’
s output is used to control valves or
other such parts, then change that control loop to manual control so that the control loop is in a state
whereby it is not influenced by the flowmeter
’
s output.
⑥
Click "OK" to change the settings to the selected values, and then click the "OK" button in the
displayed message box (Fig. 46) to complete the setting process.
Output Level
Analog Output
Pulse Output
Downscale
2.4mA
----
Zero
(
4mA, 0Hz
)
4mA
0Hz
Hold
Maintains the final measurement
value
Maintains the final measurement
value
Upscale
21.6mA
11kHz
Fig.43
Fig.44
Fig.45
Fig.46