5.9
Configure Channels - Internal Pressure Screen
The
Internal Pressure
screen enables configuration of the
internal pressure transducer readings and alarm thresholds.
Click the tick (
) to commit configuration changes to the
logger.
Read Pressure
– If selected, displays the current
pressure reading.
Name
– Defines name of the channel that will be
displayed in Primeweb.
Units
– Specifies the pressure units to be used (BAR or
PSI).
Log Every
– Defines the required logging interval for
pressure measurement data (1sec to 1 hour).
Zero
– If selected, will zero the ambient pressure offset
for the sensor.
Clear Zero
– If selected, will revert the sensor offset to
factory settings.
Alarm Settings
Alarms can be configured for the internal pressure sensor. If
an alarm is triggered, the logger will send an alert to
Primeweb immediately.
Upper Alarm Enable
– If selected, an alarm will be
triggered if the pressure value goes above that specified
by the
Upper Alarm Threshold
.
Upper Threshold (BAR) –
Defines the pressure value
above which the alarm will be triggered.
Lower Alarm Enable
– If selected, an alarm will be
triggered if the pressure value goes below that specified
by the
Lower Alarm Threshold
.
Lower Threshold (BAR) –
Defines the pressure value
below which the alarm will be triggered.
Debounce Delay
– Defines a configurable delay to
prevent multiple alarms being triggered by a single
event. A new alarm will not be triggered until the delay
time has run out after the first alarm is triggered.
Deadband Size
– Defines the pressure value that must
return to before an alarm is cleared.
XiLOG GO - Internal Pressure Screen