“Regumaq X-25”
Technical description
19
138112581-V01.10.2019
3.6 Controller terminal assignment
PWM
S1
S2
S3
100
–
240 V
T4A
50-60 Hz
R1|1 (1) A 240 V~
GND
Sika
Sensors
LIN-Bus
GND
Signal
V
10V
10V
PE N R1 PE N L' PE N
L' PE N L
IP 22
X-25
VN: 1.0
Paul-Oventrop-Straße 1
D-59939 Olsberg
L
N
PE
Illust. 7: Terminal allocation
Sensors
S1
Storage cylinder supply
Connections for the temperature sensors
with any polarity
at
terminals S1 to S3.
S2
Hot water
S3
Cold water
Control output for a high-efficiency pump
PWM
Control output for a high-efficiency pump.
Flow sensor
10 V
Connection for the flow sensor
observing the prescribed po-
larity
at the 10 V,
V
and GND terminals.
Volume flow
GND
Interface for LIN bus pump
10 V
Connection for the LIN bus pump
observing the prescribed polarity
at the 10 V, GND and signal termi-
nals.
GND
Signal
Power supply 100–240 V~ (50–60 Hz)
PE
Earth conductor
N
Neutral conductor
R1
Conductor relay 1
PE
Earth conductor
N
Neutral conductor
L‘
Phase (permanently live, fused contact)
PE
Earth conductor
N
Neutral conductor
L‘
Phase (permanently live, fused contact)
PE
Earth conductor
N
Neutral conductor
L
Power supply phase