These instructions cover installation of ICM Part No.325-HN on all split system heat pumps. The device is designed to control outdoor 
fan motor speed under low outdoor temperature conditions. It is specifically designed to control condenser fan motor speed in reponse to 
the saturated condensing temperature during operation in cooling mode only.
Parts necessary for mounting control and sensor assembly are included in the kit. Either assembly can be replaced independently of the 
other.

STEP 1- Be certain power to unit is disconnected.

STEP 2- Route sensor wire through the knockout on side plate then the right hole on E-part box

 

and over to outside row of coil (left 

side), be careful not to harm tubing (Figure 1).

STEP 5- Bind unused wire and secure it near or next to control.

STEP 6- Protect sensor wire from physical damage or wind movement where necessary.

Note

: Wiring in field installed, an insulated sleeve that meets local laws and regulations must be added to protect the wires.

Figure 3

Figure 2

Sensor

Figure 1

STEP 4- Secure sensor on the condenser coil found in STEP 2 
with the belt supplied.

Note: The sensor is delicate. Handle with care.

STEP 3- Find the coil return bend as shown in Figure 2 on which 
sensor will be mounted.

Top of coil

Top of coil

E-part box

See detail A

Side plate

Detail A

The right hole

The knockout 

2

 

Introduction

Mounting sensor

Summary of Contents for JAYLOAM001

Page 1: ...the unit Make sure all power to unit is turned off Disassembly by a non professional may cause abnormal operation or heating which may result in fire Before installing modifying or servicing system main electrical disconnect switch must be in the OFF position and install a lockout tag There may be more than 1 disconnect switch Always use a suitable warning label Follow all safety codes Thank you v...

Page 2: ...kout on side plate then the right hole on E part box and over to outside row of coil left side be careful not to harm tubing Figure 1 STEP 5 Bind unused wire and secure it near or next to control STEP 6 Protect sensor wire from physical damage or wind movement where necessary Note Wiring in field installed an insulated sleeve that meets local laws and regulations must be added to protect the wires...

Page 3: ... Defrost Control OFM Outdoor Fan Motor Field Installed need to use wire to connections Reversing valve is energized in the Heating mode For the Heat Pump Select Jumper setting please refer to ICM325HN Application Guide Connect the ground wire Low Ambient Control Box to Outdoor Unit Control Box Outdoor Fan Motor Outdoor Fan Motor Remove the fan black wire from the Deferost Control Board Connect the...

Page 4: ...und wire Low Ambient Control Box to Outdoor Unit Control Box Figure 11 Figure 9 Figure 8 Outdoor Fan Motor Connect the Outdoor Fan Motor black wire with the grey wire of the ICM325 HN Module with the terminal Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 4 Mounting control assembly Mounting electrical box Figure 10 Outdoor U...

Reviews: