Installation guidelines
19
Table 5. ACS contacts assignment
Contacts marking
Contacts assignment
LEFT, RIGHT
single pass left / right
(lowest priority)
STOP
non-authorized (mode "Stop")
(medium priority)
AP
arms folding ("antipanic")
(highest priority)
GND
common contact
Inputs for connecting of ACS differ on priorities:
AP input has the highest priority. As long as this input is closed GND
contact, arms of the turnstile are collapsed and the turnstile does not
respond (!!!) to other signals;
STOP input has the medium priority. When the input is closed on
GND contact the turnstile switches to "Stop" and does not respond to other
effects, except AP.
LEFT and RIGHT inputs have the same low priority and include a
single passage in one direction or another. If both inputs are closed,
passage is allowed in that direction the input which was closed first. If
passage was not performed the turnstile will move to "Stop" mode
automatically within 5 seconds.
CAUTION (!) In case of closure of one of STOP (or) AP inputs -
commands from the remote cannot be accepted, i.e. ACS has a higher
priority.