5.3. Connection of the control board to the ACS controller.
In some cases the turnstile CB is required to be connected directly to the
ACS controller, as passages to be enabled by the board (when unattended
by the controller) are perceived by the system as “break-in”.
In order to apply this diagram for connecting the turnstile it is
necessary to install the jumper J2 onto the cross-board (Fig. 16). If the
jumper J2 is installed, the turnstile is not responding to commands by the
board, but just transmits their status to the contacts of the terminal blocks
I/O1...I/O4 (Fig. 16) which are open-collector outputs. The contacts are
designed as per Table 6, with the board buttons numbered as shown on
Fig. 17. This group of contacts should have an output current of 150 mA at
most, with maximum allowable voltage 24 V.
Fig. 17.
Numeration of the control board buttons