background image

 

 

39 

 

10.

 

MAINTEINANCE AND WARRANTY 

 

Heat recovery Unit OXYGEN X-Air V400 is granted 24 months warranty. Make sure to have the section 
below properly filled in to confirm the installation date. Have the proof of purchase handy before 
contacting service department. 

 

Product 

 

 

OXYGEN X-Air V400 

Serial No. 

 

 

_____________________ 

Installation date 

  

_____________________ 

 

Contractor (company)  

___________________________________________________________________________ 

___________________________________________________________________________ 

 

 

(company name, technician, signature, stamp, contact details) 

 

IMPORTANT!

 Before contacting service department, make sure that the failure is persistent – check 

that: 

 

The Unit is connected to mains supply 

 

Power circuit-breaker is ON 

 

If RESET button is being displayed on touchscreen control panel (refer to section 9.2.5 "Failure 
indication") or flashing red led of control panel with a knob indicates failure (refer to section 
9.3.3 "Failure indicator"), try rebooting the Unit first. 

 

IMPORTANT!

 Flashing green and/or yellow leds of  control  panel with a  knob  do  not indicate  the 

failure!  Refer  to  section  9.3.2  "Air  filter  replacing  /  anti-frost  protection  indicator"  for  more 
information. 

 

Prepare to submit : 

 

Product model and serial number (locate it on the product label) 

 

Proof of purchase, including invoice or receipt 

 

Detailed description of failure, including photos or video recordings of the Unit, control 
panel and place of installation if necessary 

 

Your name, address, contact phone number, e-mail address 

 

Summary of Contents for X-Air V400

Page 1: ...Rev 1 1 2021 04 INSTALLATION AND OPERATION MANUAL Heat Recovery Unit OXYGEN X Air V400 ...

Page 2: ...1 ...

Page 3: ... board electrical wiring diagram 21 8 5 Description of control board contacts 22 9 OPERATION OF THE UNIT 23 9 1 WiFi controller 23 9 1 1 Downloading the app 23 9 1 2 WiFi connection set up 24 9 1 3 App home screen 26 9 1 4 Setting up weekly operation program 26 9 1 5 Ventilation boost activation 27 9 1 6 Away 27 9 1 7 Filter menu 28 9 1 8 Resetting WiFi controller to factory defaults 28 9 2 Contro...

Page 4: ... of packages matches with the consignment documentation Upon noticing any non conformity or damage of the package tears dents or compressed box detached or reattached packaging tape inform the courier immediately and indicate the disrepancies or damages in the consignment document Verify if the right product was delivered Upon noticing any non conformity inform the Sender immediately Verify if all...

Page 5: ...ery Unit OXYGEN X Air V400 1 pc Control panel 10m connection cable included or WiFi adapter 1 pc Fastening elements Mounting bracket 1 pc Condensate drain nozzle Ø32 1 pc Condensate drain gasket Ø25 1 pc Installation manual 1 pc ...

Page 6: ...tended to be used by persons including children with reduced physical sensory or mental capabilities unless they have been instructed to use the Unit and under constant supervision of person held responsible for their safety Children may only use the Unit under adult supervision Only original supplementary parts and consumables certified by manufacturer should be used The Unit package cardboard pl...

Page 7: ...2014 ES 1254 2014 ES 2017 1369 EN 13141 7 2010 2010 30 EU labelling and standard product information of the consumption of energy and other resources by energy related products ES 1254 2014 2011 65 EU restriction of the use of certain hazardous substances in electrical and electronic equipment RoHS EN 50581 2012 2014 35 EU harmonization of the laws of the Member States relating to the making avail...

Page 8: ...f heat recovery 86 2 h Maximum flow rate m3 h 400 i Electric power input of the fan drive including W 167 j Sound power level LWA 51 k Reference flow rate m3 s 0 078 l Reference pressure difference Pa 50 m Specific power input SPI W m3 h 0 22 n Control factor 0 65 Control typology Local demand control o Declared maximum leakage rate internal 1 2 external 1 1 q Position and description of visual fi...

Page 9: ...ce Pa Air flow m3 h El consumption W 100 100 400 166 9 150 381 166 0 200 356 165 1 250 329 164 0 300 300 162 3 350 266 159 1 400 224 157 6 450 179 156 2 70 50 284 76 6 75 269 76 4 100 254 76 2 125 238 75 7 150 221 75 2 175 201 73 0 200 179 71 8 0 50 100 150 200 250 300 350 400 450 500 100 150 200 250 300 350 400 450 Resistance Pa Air flow m3 h Performance curves 50 70 100 ...

Page 10: ...9 225 154 70 9 50 20 204 39 0 30 196 39 0 40 188 38 9 50 179 38 7 60 171 38 4 70 162 38 2 80 153 38 0 90 142 38 0 Measured with M5 class filters installed ...

Page 11: ...r setting Air duct Sound power level LWA Octave band Hz Total 125 250 500 1000 2000 4000 8000 50 Suppply Extract Outside Exhaust 70 Suppply Extract Outside Exhaust 100 Suppply Extract Outside Exhaust Measured according to LST EN13141 7 ...

Page 12: ...nsions and weight Figure 1 Unit dimensions Body dimensions and weight Width mm Height mm Depth mm Weight kg OXYGEN X Air V40 750 677 492 32 OXYGEN X Air V400 left side version OXYGEN X Air V400 right side version ...

Page 13: ... to humidity level indoors Disabling of supply or exhaust air stream Filtration G4 EN 779 2012 COARSE 65 ISO 16890 exhaust air filtering only G4 Carbon EN 779 2012 EPM2 5 60 ISO 16890 retains average size particles and unwanted odors M5 EN 779 2012 EPM10 50 ISO 16890 retains average size particles F7 EN 779 2012 EPM1 70 ISO 16890 retains smallest particles and pollen Visual warning of the necessit...

Page 14: ...Unit to the building s internal sewerage system Operating conditions 15oC 30oC relative air humidity 60 The Unit should be installed vertically Mounting bracket provided should be used to fasten Unit to the wall Use wall pins or locking sleeves not included depending on installation surface Use vibro isolation gaskets not included if necessary 7 2 Connecting ducts It is recommended to connect the ...

Page 15: ...tion duct incline refer to Figure 2 Air intake duct connection diagram should be ensured or other sufficient measures taken to prevent ingress of outdoor humidity or precipitation into the Unit IMPORTANT Both outside air intake and exhaust ducts and externally mounted preheater should be covered with a layer of thermal insulation of sufficient thickness to prevent condensation of humidity on their...

Page 16: ...hen firmly screw the nozzle in by hand Figure 4 Installing the condensate drain IMPORTANT Do not use pliers or other similar tools as excess power applied may damage the Unit Mechanical damage will void the warranty The necessary incline of the condensate drain pipe should be ensured during the installation at least 2 incline should be ensured in the horizontal part of the system refer to Figure 5...

Page 17: ...ject Balance the supply and exhaust air flows by adjusting values for Fan1 and Fan2 in the operating parameters setting menu of control panel with touchscreen display refer to section 1 5 of Operating parameters setting manual or using P3 and P4 controls of control panel with the knob refer to section 9 3 6 Additional system settings There is a risk of heat exchanger freezing when operating an unb...

Page 18: ...mfort functions despite similarity to any standard connectors External similarity of connectors does not guarantee compatibility connected devices may fail or damage the Unit Failure of the Unit due to incompatible supplementary parts connection will void the warranty IT IS PROHIBITED to connect or disconnect control panel or WiFi controller without turning off the mains power first The failure of...

Page 19: ...equipped with suitable power circuit breaker Power supply 230V 50Hz 5A Maximum electric power consumption fans 167W Maximum electric power consumption preheater 2000W Maximum electric power consumption heater 2000W IP protection class 20 8 2 Installation of the control panel It is recommended to install control panel of the Unit in a living space for example in a corridor or hall at 1 5 1 6 m heig...

Page 20: ...se based on readings of auxiliary CO2 or humidity sensors connected Away reduction of ventilation power while away from home by security system or external switch Function can be activated by short circuiting the respective digital contacts of RJ45 function connector Figure 8 Contacts of functions connector IMPORTANT Only passive jumpers or electric relays should be used to activate the function C...

Page 21: ...ding S2 switch does not block the usage of function refer to section 9 3 6 Additional system settings IT IS PROHIBITED to connect the functions connector directly to electrical wiring network Optional RJ45 adapter can be used for more convenient connection Figure 9 Comfort functions RJ45 connector adapter ...

Page 22: ...ontrol board electrical wiring diagram Figure 10 Control board electrical wiring diagram IMPORTANT Make sure that the Unit is disconnected from mains supply before connecting or disconnecting system components ...

Page 23: ...ity sensor AI1 DI2 function Away GND AI0 DI3 function CO2 sensor 24V Not used DI1 DI1 function Boost GND DI0 DI0 function Fire alarm GND Tach1 Exhaust fan tacho signal GND Tach0 Supply fan tacho signal GND X20 Control Panel connector X1 Exthaust air fan L X3 Exthaust and Supply fans N X7 Preheater L X10 Supply fan L X11 Preheater N K1 Bypass N K2 Not used L Bypass L L Mains L N Mains N N Not used ...

Page 24: ...it is powered Failure of the Unit or WiFi controller caused by improper connection will void the warranty 9 1 1 Downloading the app Download the OXYGEN WiFi app for your smartphone or tablet from the App store or Google Play store By downloading or using the app or WiFi controller you agree that Sviezias oras JSC collects and processes air handling unit usage data as described in the privacy polic...

Page 25: ...or 2 minutes If You fail to connect while it is active broadcasting will stop Slightly press and release immediately the hidden button through the small hole on WiFi controller body with thin screwdriver safety match toothpick to restart broadcasting IMPORTANT In case of home WiFi network device router or ADSL modem failure or any other failure to properly configure WiFi controller the broadcastin...

Page 26: ...e using browser Safari Chrome or similar by entering 192 168 4 1 in the address field Make sure that your device smartphone or tablet is connected to OXYGEN_xxxxxx WiFi network you may be asked to confirm connection by hitting use without internet or similar button IMPORTANT If it is necessary to control the Unit without connecting it to home WiFi network change the standard system password immedi...

Page 27: ...en of control app 9 1 4 Setting up weekly operation program Up to 4 different ventilation modes can be set for each day of week Set the desired operation program for the selected day or days of the week select single or multiple week days select day or days depending on above selection set operating mode start time and ventilation intensity for each slot click SAVE to apply or RELOAD to discard ch...

Page 28: ... Ventilation boost activation After the selected time previously set or scheduled ventilation intensity will be activated 9 1 6 Away Activate selected decreased ventilation intensity until the selected date The feature is useful when leaving home for a weekend or vacation select return date select return time select ventilation intensity activate selected decreased ventilation intensity by clickin...

Page 29: ... clicking RESET button order replacement filter set by clicking troley icon Figure 18 Filter menu 9 1 8 Resetting WiFi controller to factory defaults If it is necessary to reset WiFi controller to factory defaults click and hold the hidden button through the small hole of WiFi controller body with thin screwdriver safety match toothpick until the yellow light will fade away You will have to reconn...

Page 30: ... touchscreen display 9 2 1 Standby mode Touchscreen display of control panel will only display the time of day in standby mode if the Unit is switched off If the Unit is in operation settings of desired temperature and ventilation intensity will also be displayed Figure 20 Control panel with touchscreen display in standby mode the Unit is switched off the Unit is in operation ...

Page 31: ...valve state depends on device configuration Preheater state This menu enables to Activate the boost mode by single touch of button Access the settings menu Set the desired room air temperature Set the desired ventilation intensity 9 2 2 1 Winter mode Outside air temperature display depends on ambient conditions If outside air temperature is above 0 C the outside air temperature is being displayed ...

Page 32: ... cold season air supplied to the room can be additionally heated by a separately purchased duct heater installed in the ventilation system IMPORTANT Availability of feature depends on device configuration to be selected prior ordering the Unit 9 2 3 Settings menu Figure 22 Settings menu Control panel settings menu enables to Set system date and time Select menu language English Russian Polish Lith...

Page 33: ...mode settings menu Weekly operation program will be saved by clicking back arrow button IMPORTANT Click on the round button next to schedule button in main menu to activate a weekly operation program Green color of button means the program is active Toggle to deactivate 9 2 5 Failure indication In case of Unit component failure the RESET button will appear in main menu Failed component icon will t...

Page 34: ...urer of the Unit or its local representative You may control the Unit by app installed on smartphone or tablet by purchasing the WiFi controller 9 3 Control panel with a knob Control panel with a knob makes it possible to gradually control the ventilation intensity Colored LEDs indicate status of the Unit Figure 25 Control panel with a knob 9 3 1 Operating state indicator Flashing green led indica...

Page 35: ...ir filters IMPORTANT Higher than usually power consumption is to be expected when the Unit is operating in this mode 9 3 3 Failure indicator The flashing red led indicates that failure of the Unit component was detected flashes 1 time failure of outside air temperature sensor flashes 2 times failure of exhaust air temperature sensor flashes 3 times failure of supply air temperature sensor flashes ...

Page 36: ...fter the Unit reset procedure has been performed contact manufacturer of the Unit or its local representative 9 3 5 Resetting the filter lifetime meter Filter lifetime meter has to be reset after air filters have been replaced Gently press and release the hidden button through the small hole on the side of control panel S1 with thin screwdriver safety match toothpick making the yellow led switch o...

Page 37: ...e setting P2 boost mode power setting P3 supply fan power adjustment P4 exhaust fan power adjustment S1 reset button S2 switches for disabling OFF or activating ON boost 1 and away 2 functions Figure 27 Additional settings for control panel with a knob You may control the Unit by app installed on smartphone or tablet by purchasing the WiFi controller ...

Page 38: ...ing air filters Shut down the Unit by control panel make sure that fans have completely stopped Open the lid of the filter that you intend to change marked by OXYGEN by firmly gripping it and pulling out Use fabric handle to remove a filter Insert a new filter following ventilation flow direction indicated on filter frame it should point downwards Firmly push the lid of the filter back to its plac...

Page 39: ...ers can result in ventilation power decrease and higher than usually power consumption IMPORTANT Only original manufacturer recommended filters should be used The use of low quality third party filters can result in damage to sensitive device components due to excess dust or humidity Metal filter frames can cause unrestorable damage to Units body Failure of the Unit caused by the use of non origin...

Page 40: ...lure is persistent check that The Unit is connected to mains supply Power circuit breaker is ON If RESET button is being displayed on touchscreen control panel refer to section 9 2 5 Failure indication or flashing red led of control panel with a knob indicates failure refer to section 9 3 3 Failure indicator try rebooting the Unit first IMPORTANT Flashing green and or yellow leds of control panel ...

Page 41: ...40 After gathering all the necessary information contact the point of purchase ...

Page 42: ...ras JSC Company code 304288834 VAT code LT100010366918 Bank account LT42 7044 0600 0810 3886 SWIFT CBVILT2X AB SEB bank Address Birzelio 23 osios g 23G 50220 Kaunas Lithuania Phone No 370 627 26666 oxygenvent www oxygenvent com ...

Reviews: