10
Daisy-chain connector cables have a 5-pin
female connector on one end, and a 3-pin
male connector on the other end. The 3-pin
male connector on the cord must be installed
into the corresponding 3-pin female “power
out” connector on the luminaire. The 5-pin
female connector must be installed into the
corresponding 5-pin male “power in” connector
on the luminaire.
3-pin
male connector
5-pin
female connector
When luminaires are mounted consecutively,
the distance between each luminaire must be a
minimum of 8.25 in. (210 mm).
4
Continue until daisy chain is complete.
Always ensure that cords are:
• not concealed or extended through a wall,
floor, ceiling, or other parts of the building
structure,
• not located above a suspended ceiling or
dropped ceiling,
• not permanently affixed to the building
structure,
• routed so that they are not subject to strain
and are protected from physical damage,
• visible over their entire length, and
• used within their rated ampacity as
determined for the maximum temperature
of the installed environment specified in the
instructions.
5
Ensure that connector cap remains firmly installed
in last luminaire of daisy chain string to ensure
safe operation and IP66 integrity.
WARNING
Both connectors on the luminaire must be sealed
(either with a power cord, daisy-chain connector
cord or a cap) once installed. Use of luminaire(s)
with exposed connectors will void the product
warranty.
6
Switch on the branch curcuit.
ATTENTION
Daisy Chain Guide
Max # Luminaires / String
Connector Cable Length
3 ft
6 ft
10 ft
15 ft
Voltage
208 V
3
2
2
1
240 V
7
7
7
7
277V
8
8
8
8
347 V
10
10
10
10
400 V
12
12
12
12
10 cm
10 cm
8.25 in
(210 mm)
8.25 in
(210 mm)
ATTENTION