Computer addressable emergency lighting unit

with integrated LED converter for LED lighting

BATT

Power

LED

LED

RED

RED

LED

350mA max 11V

Operating time

3h

Batt.

NiCd 2.4V / 1.5-1.8Ah

Mains 220-230V +/- 10% / 50-60Hz

LED voltage - SELV - max. 25V

BUD

KRMT 33/62

1

30

5

4

Wire Key

= Live

= Switch Live

= Nutural

= =Earth

= Coms 1

= Coms 2

Take the KLIPPA out of the box and unscrew the x2No. retaining
screws on the front and unclip the diffuser from the housing. Do

 NOT

remove the screw from the diffuser, there are retainer washers fitted

to aid re-installation.

Removing Diffuser & Gear Tray

Fixing to Conduit Box, Wall or Ceiling

The KLIPPA Bulkhead has been designed to incorporate different

mounting methods. Below are examples of the two most common.

Wiring Detail

Wire the connector block as per the

label guides. In case of maintained
operation the switched live must be
connected to the LSW terminal. Note

the switched live and the unswitched

live must be from the same phase.

Plug the battery connectors together
(Red and Black Cables), ensuring
polarity is correct.

1

Remove the x2No. Gear Tray retainer screws (see
Fig 2.) and unclip the Gear Tray from the housing
unit using a flat bladed screw driver (See Fig 3.)

2

Fig 2.

3

Fig 3.

Fig 1.

Conduit Box Mounting

a

Identify which way the KLIPPA
Bulkhead needs to be mounted by
looking at the Conduit Box fixing
holes and position. See Fig 4.

Ceiling and Wall Mounted

Drill out the required holes and use suitable fixings to secure the fitting to

the wall or ceiling. For IP65 KLIPPA Bulkhead, ensure that you use
suitable IP65 fixings.

The KLIPPA Bulkhead housing contains dimples for various
differentconduit sizes. Choose the size that relates to your conduit box
and drill out a suitable sized hole (see Fig 5.) for the fixing screws (not
supplied) and a centre hole for the cable.

b

Fig 4.

Fig 5.

Battery Connection

4

Conduit gasket will be
required for IP65 KLIPPA
Bulkheads in order to
maintain it's water
resistance.

Fig 6.

Non Maintained

Maintained

N

L

N

L

Lsw

If fitted see product specification

N

L

Lsw

As fig 5.

Apply mains supply to test the luminaire. The indicator LED will show
flashing green and the LEDs will illuminate if the Switched Live supply

is connected and switched on.

To test, briefly fail the supply to illuminate sign from the internal

battery. The indicator LED will be extinguished.

Applying Mains Supply

Test Emergency Supply

Reconnect Mains Supply

Reconnect the unswitched supply to restart battery charging,
indicated by the flashing green indicator LED. Reconnection of the
Switched Live will re-illuminate the LEDs from the mains supply if
connected for maintained operation.

5

6

7

Installation Instructions

KLIPPA Bulkhead luminaires are fully automatic self testing emergency
lighting luminaires and do not require a key switch testing facility.

1. Luminaires should only be installed by suitably qualified personnel.

2. Installation should be carried out in accordance with the requirements
of BS7671 and luminaires located as required by BS5266 Pts 1, 7 and 8.

3. Before installing, connecting or servicing these luminaires, isolate the
mains supply to which they are to be connected.