28 |
P a g e
Power requirements
Main Circuit: 10V-36V DC
Inputs: 10V-36V DC
Outputs
Load: 3-30V DC, max. 4A/channel, constant voltage PWM dimming
Inputs
Type: 12 x galvanically isolated, noise protected common GND digital inputs for
dry contacts or open collector transistor outputs
Terminals
Type: Screw terminals for max. 2.5 mm
2
wires
Communication
10Mb/s Ethernet via RJ45 Ethernet connector
Simple ASCII based TCP commands, number of socket connections that are
allowed to be opened simultaneously: 4
HTTP via built-in web server
Other parameters
Dimensions: W x H x D = 157 mm x 86 mm x 57 mm (9 DIN unit width)
Standards
EN 60669-2-1, EN 55015:2013, EN 61547:2009, EN 61347-1, EN 61347-2-13, RoHS
Test methods
EN 55016-2-3:2010, EN 55022:2010/AC:2011, EN 61000-4-3:2006/A1:2008/A2:2010
EN 61000-4-6:2009, EN 61000-4-4:2005/A1:2010, EN 61000-4-2:2009