One-Touch™ Test Mode
Test
Action
Observation
Normal
Operation
GREEN system status LED flashes at
normal rate.
RED and GREEN input status LEDs off.
GREEN output status LED off.
One-
Touch™
View Mode
Hold down One-Touch™ button for
less than 2 seconds.
Note:
Automatically exits after 2
minutes.
GREEN system status LED flashes at
twice normal rate.
Unconfigured system:
All RED LEDs
will flash briefly three times and test mode
is exited.
Configured system (expected)
RED LED = tamper state.
GREEN LED = active state/normal
output.
GREEN LED off = non-active
state/unconfigured input.
View mode is intended for a configured system. See
help for more information.
One-
Touch™
Active
Mode
CAUTION:
Disconnect any output relays that should not be triggered before entering
Active
mode.
Hold down One-Touch™ button for 2
to 4 secs.
GREEN system status LED flashes four
times faster than normal.
Trigger each input sensor in turn and
ensure that the LEDs indicate the
correct state.
Note:
The controller will operate
unconfigured and no system
communications will occur.
The first change in state will be latched and the display for
that input will not change until test mode is exited.
Green - Red
2-State
4-State
N/A
Input open
N/A
Input closed
Input open
Input open
tamper
Input closed
Input
tamper
short
Green - Red
3-State NO
3-State NC
N/A
N/A
Input open
Input closed
Input closed
Input open
Input open tamper
Input
tamper
short
>
>
GREEN output LED is on/off for a 5
second cycle (relays active/inactive)
Exit One-
Touch™
Active Test
mode
Hold down One-Touch™ button for
less than 2 seconds. One-Touch™
Test mode will automatically be timed
out after 1 hour, power up or power
down.
GREEN flashes at normal rate again.
All other status LEDs off.
– Page 5 of 22 –