Page
15 of 39
Number
SM001-300
HVAC: Idle Management System
Unit runs correctly, but
less than expected run
time.
1. Ground terminal(s).
2. Batteries weak or not
charged correctly.
3. High amperage draw.
4. Check battery Man-
agement System.
5. Check Battery Sep-
arator.
1. Inspect and tighten ALL connections.
2. Check batteries for condition and state of charge. Check
service screens in EHVAC control. See “
3. Check amp draw in EHVAC control service screen or
use DC ammeter to check amps when running. Exces-
sive amperage could signal compressor or internal com-
ponent issue.
Amperage ranges 40 to 75 depending
on settings and conditions
.
4. Check battery management device, harness and sep-
arator.
5. Same as 4.
Unit is noisy or vibrates.
1. Evaporator Blower
motor.
2. Condenser fan motor.
3. Compressor mount-
ing.
4. Compressor internal.
1. Check evaporator blower. See “
Motor and Linear Power Module Testing
2. Check condenser fan. See “
3. Check rubber compressor mounts. See “
4. If rubber compressor mounts check out acceptable, and
compressor vibrates excessively, call your local dealer
for support.
Table 1.
A/C System Diagnostic
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
/
“Appendix” on page 18.