background image

VT_user manual-eng / rev.04                                                                                                                                                                  Page 3 – April 2015 

 

 

VT_user manual-eng 

 

 

 

 

CAPACITY 

WEIGHT 

(*)

 

CONNECTIONS 

 

litres 

kg 

E-U 

T / SD 

SF / S 

inches 

inches 

inches 

100 

25 

1”¼   

½” 

1”¼ 

200 

40 

2” 

½” 

1”¼ 

300 

50 

2”½  

½” 

1”¼ 

500 

70 

3” 

½” 

1”¼ 

800 

90 

3” 

½” 

1”¼ 

1000 

105 

3” 

½” 

1”¼ 

1500 

200 

3” 

½” 

1”¼ 

2000 

240 

3” 

½” 

1”¼ 

2500 

280 

3” 

½” 

1”¼ 

3000 

300 

4” 

½” 

1”¼ 

4000 

450 

4” 

½” 

1”¼ 

5000 

530 

4” 

½” 

1”¼ 

(*)

  Indicative value, valid only for transportation and handling purposes

 

 
 

Description 

 

The Pacetti VT series of chilled water vessels are utilised to store chilled water produced by an external chiller or chilled source.  

There are 5 models with 2 of the models fitted with flow dividers or a perforated plate to avoid flow paths. 

All models are provided as standard with threaded connections, but may be also equipped with flanged connections on request. 
These chilled vessels are available both in black carbon or galvanized steel and stainless steel. 

The black carbon steel tanks are used in case of indoor installation, therefore it is not required any kind of coating against corrosion. 
The galvanized steel tanks can be also used in case of outdoor installation, when it is necessary to ensure corrosion and weather protection. 
The stainless steel tanks are treated with pickling process and are suitable for indoor or outdoor installations. 

All models can be manufactured in vertical or horizontal arrangement. 
 

 

 

Protection coating against corrosion 

 

HOT DIP GALVANIZING 

This kind of coating is performed on carbon steel vessels by immersion of the tank in a molten zinc bath at 450°C according to UNI EN ISO 1461. 

 

METAL PICKLING  

It’s a metal surface treatment used to remove impurities after manufacturing processes. The tank is dipped into a solution called pickle liquor which contains strong acids able 
to remove contaminants.  

 

 

Thermal insulation against condensation 

 

HARD FOAM POLYURETHANE 
 

Hard foam polyurethane injected 
Made of hard foam polyurethane 30mm thick, density of 40 to 42 kg/m3, average conductivity of 0.024 W/mK. CFC and HCFC free. 

Closed cell elastomer foam 

Made of closed cell elastomer foam sheets 20mm thick, density of 30 kg/m3, average conductivity of 0.034 W/mK. CFC and HCFC free. 

 

Insulation 

Tank capacity 

Density 

Thermal conductivity coefficient 

Hard foam polyurethane injected 30 mm  

100 ÷ 1000 l

 

40÷42 kg/m3

 

 = 0,024 W/mK 

Closed-cell elastomer foam 20 mm 

1500 ÷ 5000 l 

30 kg/m3 

 = 0,034 W/mK 

 

 

External cladding is available in coloured PVC with zipper fastening or embossed aluminium 0.4mm thick for outdoor installations. 

 

 

 

Operation 
 

The Pacetti VT series of chilled water vessels are used in air conditioning and cooling systems when the water content of the plant is reduced. When installed between user and 
chillers, these tanks can limit frequent compressor starts and allow a regular functioning of the plant at a constant temperature, avoiding timer intervention. 

 

 

 

 

 

 

Models 

 

The Pacetti VT series of chilled water vessels are available in different models: 
 

VT-G  

Black carbon steel  

VT-Z    

 Galvanized steel  

VT-X    

 Stainless steel 316  

VTS      

 Black carbon steel with perforated central divider plate 

VTP      

 Black carbon steel with multiple flow dividers  

 

 

 

 

 

 

Conformity 

 

The Pacetti VT series of chilled water vessels are made with automatic welding processes.  

All manufacturing processes are guaranteed by the Quality Management System of the Company, certified to ISO 9001. 
All Pacetti products are subject to hydraulic tests at 1.5 * maximum working pressure and comply with the following standard: 

European Pressure Equipment Directive 97/23/CE – Art.3.3

 (pressure vessels) - excluded from CE mark. 

 

 

 

Cooke Industries - Phone: +64-9-579 2185  Fax: +64-9-579 2181  Email: sales@cookeindustries.co.nz  Web: www.cookeindustries.co.nz

Summary of Contents for VT-G

Page 1: ... T T G G G V V VT T T Z Z Z V V VT T T X X X V V VT T TS S S V V VT T TP P P Chilled water buffer vessels USER AND MAINTENANCE MANUAL Cooke Industries Phone 64 9 579 2185 Fax 64 9 579 2181 Email sales cookeindustries co nz Web www cookeindustries co nz ...

Page 2: ...Outlet T Thermometer SD Sensor SF Vent S Drain Dimensions VERTICAL OPEN BUFFER VESSELS VERTICAL BUFFER VESSELS WITH PERFRORATED CENTRAL DIVIDER PLATE VERTICAL BUFFER VESSELS WITH MULTIPLE FLOW DIVIDERS VT G VT Z VT X 30 mm hard foam PU insulation 100 1000 l VT G VT Z VT X 20 mm closed cell elastomer insulation 1500 5000 l VT S 20 mm closed cell elastomer insulation 300 2000 l VT P 20 mm closed cel...

Page 3: ...move contaminants Thermal insulation against condensation HARD FOAM POLYURETHANE Hard foam polyurethane injected Made of hard foam polyurethane 30mm thick density of 40 to 42 kg m3 average conductivity of 0 024 W mK CFC and HCFC free Closed cell elastomer foam Made of closed cell elastomer foam sheets 20mm thick density of 30 kg m3 average conductivity of 0 034 W mK CFC and HCFC free Insulation Ta...

Page 4: ...PLE Closed circuit plant with chilled water storage tank installed on return Description A1 Heat pump air conditioner split system A2 Heat pump air conditioner monoblock B External unit C Fan coil unit D Pump E Expansion vessel F Storage tank Installation in a double circuit plant Cooke Industries Phone 64 9 579 2185 Fax 64 9 579 2181 Email sales cookeindustries co nz Web www cookeindustries co nz...

Page 5: ... in order to perform future maintenance verify that the room where the tank is placed has openings of a size to allow the free passage of the vessel in case it s necessary to bring it out in order to avoid any demolition 1 3 START The connection diagram shown in this document is purely indicative and not binding it s up to the designer of the system to give the best connection scheme for the requi...

Page 6: ...lcohol is not recommended 3 DEFECTS AND FAILURES PROBLEM CAUSE SOLUTION Excessive pressure inside the tank Expansion vessel lack or malfunctioning The pressure of the expansion vessel air cushion is not enough Verify that the system is equipped with an expansion vessel If the expansion vessel is present check that the precharge pressure is set correctly it must be restored to the initial valued sl...