010604-16

FUSION_D1

15

Label

MADE IN CANADA

CERTIFIED FOR CANADA AND U.S.A.
LISTED ROOM HEATER, SOLID FUEL TYPE.
ALSO FOR USE IN MOBILE HOMES
TESTED TO CAN/ULC S627-M93 AND UL 1482-98

MODEL   SERIES D:

 FUSION

260504

5050.7623

FSND-1

A. SIDEWALL TO UNIT

19 in. / 483 mm

15 in. / 381 mm

15 in. / 381 mm

15 in. / 381 mm

17 in. / 432 mm

17 in. / 4.32 mm

B. BACKWALL TO UNIT

13.5 in. / 305 mm

<

<

<

<

<

 9.5 in. / 241 mm

6.5 in. / 165 mm

6.5 in. / 165 mm 11.5 in. / 292 mm

9.5 in. / 241 mm

C. CORNER TO UNIT

11.25 in. / 286 mm 11.25 in. / 286 mm

4.25 in. / 108 mm 4.25 in. / 108 mm

N/A 8.25 in. / 210 mm

D. SIDEWALL TO CONNECTOR

27 in. / 685 mm

23 in. / 585 mm

22.5 in. / 570 mm 22.5 in. / 570 mm 24.5 in. / 620 mm 24.5 in. / 620 mm

E. BACKWALL TO CONNECTOR

19 in. / 485 mm

<

<

<

<

<

 15 in. / 380 mm

11.5 in. / 292 mm  11.5 in. / 292 mm 16.5 in. / 420 mm 14.5 in. / 370 mm

F. CORNER TO CONNECTOR

22 in. / 560 mm

22 in. / 560 mm

14.5 in. / 370 mm 14.5 in. / 370 mm

N/A 18.5 in. / 470 mm

DO NOT REMOVE THIS LABEL

• INSTALL AND USE IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION AND OPERATING INSTRUCTIONS.
• CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS, INSTALLATION PERMIT AND INSPECTION IN

YOUR AREA.

• DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE (USA. ONLY).
• USE 6 INCH / 150MM DIAMETER MINIMUM 24 MSG BLACK OR LISTED CONNECTOR.
• CONNECT TO A LINED MASONRY CHIMNEY SUITABLE FOR USE WITH SOLID FUELS.
• DO NOT OBSTRUCT THE SPACE BENEATH THE HEATER.
• SEE LOCAL BUILDING CODE AND MANUFACTURER'S INSTRUCTIONS FOR PRECAUTIONS REQUIRED WHEN PASSING

A CHIMNEY THROUGH A COMBUSTIBLE WALL OR CEILING.

• DO NOT PASS A CHIMNEY CONNECTOR THROUGH A COMBUSTIBLE WALL OR CEILING.
• MINIMUM CLEARANCE BETWEEN SINGLE WALL CHIMNEY CONNECTOR AND COMBUSTIBLE MATERIALS-18INCHES/

455MM.  CLEARANCE MAY BE REDUCED BY THE USE OF LISTED PIPE SHIELDS, WALL PROTECTORS OR OTHER
MEANS APPROVED BY LOCAL BUILDING OR FIRE OFFICIALS.

HORIZONTAL CONNECTOR NOT PERMITTED IN MOBILE HOMES

<

<

<

<

<

AS TESTED - PIPE SHIELD MAY BE REQUIRED BY LOCAL AUTHORITIES.

* COMBUSTIBLE ALCOVE SIZE : DEPTH - 4 FT. / 1.22 M MAXIMUM, HEIGHT 7 1/2 FT. / 2.3 M MINIMUM

COMBUSTIBLE FLOOR MUST BE PROTECTED BY A CONTINUOUS NON-COMBUSTIBLE MATERIAL EXTENDED TO THE
FRONT, SIDES AND BACK AS INDICATED.

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS

COMPONENTS REQUIRED FOR MOBILE HOME AND ALCOVE INSTALLATION: OUTSIDE AIR KIT, AND ONE OF THE
FOLLOWING LISTED CONNECTORS:  SECURITY MODELS DP OR DC,  OLIVER MACLEOD MODEL PV,  ENERGY VENT
E VENT,  SELKIRK METALBESTOS MODEL DS,  METAL FAB MODEL DW,  AMERI-TEC MODEL DBSP,  INDUSTRIAL
CHIMNEY MODEL EXCEL ULTRA-BLACK, OR  SIMPSON DURA-VENT MODEL DVL IN COMBINATION WITH ONE OF THE
FOLLOWING COMPATIBLE CHIMNEY SYSTEMS:   APPLIANCE MUST BE INSTALLED WITH PEDESTAL OR LEG KIT
ATTACHED.

IN CANADA -  SECURITY MODEL S2100,  OLIVER MACLEOD PROJET MODEL HT 3000,  SELKIRK SENTINEL MODEL CF,

INDUSTRIAL CHIMNEY MODEL EXCEL 2100.

IN USA -  SECURITY MODEL ASHT OR S2100,  OLIVER MACLEOD MODEL 3103 OR HT 3000,  SELKIRK METALBESTOS

MODEL SS II,  METAL FAB MODEL 2100,  AMERI-TEC MODEL HS,  INDUSTRIAL CHIMNEY MODEL EXCEL 103HT,
SIMPSON DURA-VENT MODEL DURA/PLUS AND DURA TECH.
USE COMPONENTS SPECIFIED IN PACIFIC ENERGY INSTALLATION INSTRUCTIONS.

OPTIONAL COMPONENTS - WATER COIL (CANADA ONLY), FAN KIT #SSER.BLOW, FAN ELECTRICAL RATING: 115V,
60HZ, 80WATTS.  DO NOT ROUTE POWER CORD BENEATH HEATER.

CAUTION: RISK OF EXCESSIVE TEMPERATURES - KEEP ASH DUMP CLOSED DURING FIRING OF THE HEATER.

OPERATE ONLY WITH FEED DOOR CLOSED.  OPEN TO FEED FIRE ONLY.

KEEP FURNISHINGS AND OTHER COMBUSTIBLE MATERIALS WELL AWAY FROM HEATER.

REPLACE GLASS ONLY WITH CERAMIC GLASS.

J   F   M   A

  M   J   J   A   S   O N   D

2004

2005

2006

2007

2008

2009

DATE OF MANUFACTURE

MANUFACTURED BY:

PACIFIC ENERGY FIREPLACE PRODUCTS LTD.

PO. BOX 1060, DUNCAN, BC  V9L 3Y2

HOT WHILE IN OPERATION.  DO NOT TOUCH.  KEEP CHILDREN,
CLOTHING AND FURNITURE AWAY.  CONTACT MAY CAUSE SKIN
BURNS.  SEE NAMEPLATE AND INSTRUCTIONS.

U.S. ENVIRONMENTAL PROTECTION AGENCY
CERTIFIED TO COMPLY WITH
JULY, 1990, PARTICULATE
EMISSION STANDARDS

WH-

WH-

CAUTION

IN CANADA

G.

18 INCHES / 455 MM

H.

8 INCHES / 200 MM

I.

8 INCHES / 200 MM

IN U.S.A.

G.

16 INCHES / 405 MM

H.

5 INCHES / 127 MM

I.

0 INCHES / 0 MM

* ALCOVE

INSTALLATION

USING

DOUBLE WALL

CONNECTOR

RESIDENTIAL INSTALLATION

USING SINGLE WALL CONNECTOR

MOBILE HOME

INSTALLATION

USING

DOUBLE WALL

CONNECTOR

VERTICAL CONNECTOR     HORIZONTAL CONNECTOR

VERTICAL CONNECTOR HORIZONTAL CONNECTOR

RESIDENTIAL CLOSE CLEARANCE

INSTALLATION

USING DOUBLE WALL CONNECTOR

C

F

ADJACENT WALL

E

B

A

SIDE WALL

D

H

SIDE

FRONT

H

SIDE

G

BACK  I

HEATER

BACK WALL

ADJACENT WALL

Summary of Contents for Fusion

Page 1: ...TION OPERATION GUIDE Design D Model FUSION PLEASE SAVE THESE INSTRUCTIONS SAFETY NOTICE Ifthisstoveisnotproperlyinstalled a house fire may result For your safety follow the installation instructions C...

Page 2: ...on 8 Clearances 8 Chimney and Connector 8 Double Wall Connector 8 Single Wall Connector 8 Procedure 8 Floor Protector 9 Combustion Air 9 Operation 10 Wood Selection 10 How to Test Your Wood 10 Lightin...

Page 3: ...nwoodandtoo slow a burning rate This heavy deposit is building up at least as quickly in the chimney WARNING ONLY USE MATERIALS SUPPLIED BY MANUFACTURER WHEN DOING MAINTE NANCE OR REPLACEMENTS 4 DOOR...

Page 4: ...ust be lived with Regular inspection and cleaning is the solution The use of dry seasoned wood and ample com bustion air will help to minimize the buildup Chimney Fires The result of excessive creosot...

Page 5: ...9 8 1 4 8 1 4 4 1 4 4 1 4 18 22 11 1 4 11 1 4 25 22 1 4 36 1 4 23 1 2 26 3 4 8 3 8 33 1 2 Minimum Clearance to Combustibles FIG 1 Double Wall Connector Residential Single Wall Connector Residential Al...

Page 6: ...instructions 7 Attach stove to flooring using two 1 4 x 2 or longer lag screws Warning Under no circumstances is this heater to be installed inamakeshiftor temporary manner Itmaybefiredonlyafter the...

Page 7: ...el DBSP 3 Energy Vent 7 Industrial Chimney Model Excel Ultra Black 4 Selkirk Metalbestos Model DS 8 Simpson Dura Vent Model DVL B As well as one of the following compatible chimney systems All parts 6...

Page 8: ...meetalllocalcodes Donotconnectthisunittoachimney flue serving another appliance Minimum system height is 15 feet 4 6 m measured from base of appliance Double Wall Connector Use a listed double wall co...

Page 9: ...ct Outside air may also be ducted from outside through the 4 diameter knockout hole in the rear of the pedestal enclosure Note Thisunitisnotdesignedtobeoperatedwiththefiring door open In addition to t...

Page 10: ...very important that the room be well ventilated Open all windows and doors Smoke and fumes caused by the curing process may cause discomfort to some individuals Lighting a Fire WARNING Never use chem...

Page 11: ...ler Re install baffle assembly in reverse order The two side pieces of insulation must be tight against the siderails Restarting After Extended or Overnight Burns 1 Open door and rake hot embers towar...

Page 12: ...firebox 8 Install the two screws through the flange of the blower into the rear shield 9 Plugthepowersupplycordinandcheckbloweroperation Power Cord Clearance Tab Temperature Switch Blower Operation Pr...

Page 13: ...dup See 1 2 3 above Low Heat Output 1 Wood is wet Use dry wood 2 Fire too small Build a larger fire 3 Draft too low Chimney plugged or restricted inspect and clean Won t Burn Overnight 1 Air control i...

Page 14: ...ost Manifold 4105 All parts may be ordered from your nearest Pacific Energy dealer Contact Pacific Energy for the location of the dealer nearest you 12a Firebrick 1 1 2 x 4 1 2 x 1 1 4 1 pc 248 12b Fi...

Page 15: ...ACK AS INDICATED MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS COMPONENTS REQUIRED FOR MOBILE HOME AND ALCOVE INSTALLATION OUTSIDE AIR KIT AND ONE OF THE FOLLOWING LISTED CONNECTORS SECURITY MODELS DP O...

Page 16: ...PACIFIC ENERGY FIREPLACE PRODUCTS LTD 2975 Allenby Rd Duncan BC V9L 4T8 Phone 250 748 1184 Web site http www pacificenergy net...

Reviews: