Servicing of the stove can be performed from the rear of the unit by removing the access panel from the unit.
Caution: The gas line should be installed by a qualified service person in accordance with all building codes.
This section is intended as a guide for qualified technicians installing this stove. Consult local and/or national
building codes before proceeding.
•
Gas supply line connection is located on the rear of the stove. Gas connection accepts a ½” 45° flare
fitting. Correct gas line diameter must be used to assure proper operation and pressure.
•
The stove input rating is shown in the chart below.
•
A drip leg must be installed in the gas supply line going to the gas control valve to minimize the possibility
of any loose scale or dirt within the gas supply line from entering the control valve.
•
It is essential that a union or flanged connection be installed just upstream of the valve to allow for repair
or replacement of the gas valve.
Check local codes for additional requirements.
Turn on the gas supply and check that all connections are tight and leak free.
Gas Supply
Mirage
Gas Orifice Output
AFUE
NG
1.98mm 30,000 btu/hr
72%
LP
1.25mm 28,000 btu/hr
72%
Please refer to following page for gas pressure testing procedure.
Gas Pressure Check
Gas pressure requirements
Input Pressure
Natural Gas Propane
Minimum 4.0” WC
11.0” WC
Maximum 13.9” WC
13.9” WC
Manifold Pressure
High
3.5” WC
10” WC
Low
1.6” WC
6.4” WC