Fig #2
SINGLE WALL
CONNECTOR
375mm
350mm
527mm
660mm
250mm
250mm
570mm
Minimum Clearances to Combustibles
Fig #2a
SINGLE WALL
CONNECTOR
WITH SHIELD
250mm
350mm
400mm
660mm
200mm
200mm
520mm
Minimum Clearances to Combustibles
©PACIFIC ENERGY FIREPLACE
PRODUCTS LTD.
Fig #3
Non-combustible floor
protector
[300mm]
[781mm]
[723mm]
[200mm]
[200mm]
Minimum Width - 781mm
Minimum Overall Depth - 723mm
Minimum Thickness - 6mm
The stove may be installed on a combustible floor
provided ember protection made from a 6mm
thick non-combustible fibre-cement board with a
thermal conductivity value of .41 W/m degree K .
This protection must extend as follows:
300 mm on the firing side and 200mm both sides
of the door opening. See Figure #3.
8
010515-20 ALT4
Clearances
Floor Protector