©PACIFIC ENERGY FIREPLACE
PRODUCTS LTD.
Chimney and Connector
WARNING: INSTALL CHIMNEY AND ALL COMPONENTS OF CHIMNEY SYSTEM ACCORDING
TO CHIMNEY MANUFACTURER’S INSTRUCTIONS.
Connect to a listed chimney complying with the requirements of AS/NZS2918/2001 and a chimney
suitable for use with solid fuel that is lined and in good condition and meets local building codes.
The chimney flue size should be the same as the stove outlet for optimal performance. Reducing or
increasing the flue size may adversely affect stove performance. Chimney flue exit is to be minimum
1000mm above roof and 600mm above highest projection within 3000mm. The installation must
meet all local codes. Do not connect this unit to a chimney flue serving another appliance. Minimum
system height is 4600mm (measured from base of appliance).
Installation Procedure
1. Install all components to the chimney manufacturer's installation requirements. (Outside
combustion air may be required, consult local building codes. See Combustion Air section on
page 11.)
2. Installed with the crimped or male ends pointing down. This will carry any liquid creosote or
condensation back into the stove.
3. If a roof or ceiling support is used in the installation, you will find the chimney manufacturer's
complete instructions packed with the roof support.
4. To start installing smoke pipe (chimney connector), slip crimped edge of the pipe inside the
stove collar. Use holes provided in collar to secure pipe with three screws.
5. Install the remaining lengths of pipe, one on top of the other, to the finished height of the chimney
connector and secure to each other.
9
010515-20 ALT4