SECTION 2 SPECIFICATIONS
10
2.1.1 INPUT POWER REQUIREMENTS (cont.)
MODEL 160-AMX
INPUT VOLTAGE AND INPUT CURRENT
The Model 160-AMX three phase input voltages, required input currents at full rated load and
recommended service input currents are stated as below.
INPUT
CURRENT
(360-440 Hz optional)
INPUT
CURRENT
SERVICE
RECOMMENDED
1) 208
VAC
∆
±10%, 47-63 Hz
28 A
rms
40
A
2) 220
VAC
∆
±10%, 47-63 Hz
26 A
rms
40
A
3) 230
VAC
∆
±10%, 47-63 Hz
25 A
rms
40
A
4) 240
VAC
∆
±10%, 47-63 Hz
25 A
rms
40
A
5) 220/380 VAC ±10%, 47-63 Hz
15 A
rms
20
A
6) 230/400 VAC ±10%, 47-63 Hz
14 A
rms
20
A
7) 240/416 VAC ±10%, 47-63 Hz
14 A
rms
20
A
( cost option )
8) 277/480 VAC ±10%, 47-63 Hz
14 A
rms
20
A
MODEL 305-AMX
INPUT VOLTAGE AND INPUT CURRENT
The Model 305-AMX single phase input voltages, required input currents at full rated load and
recommended service input currents are stated as below.
INPUT
CURRENT
(360-440 Hz optional)
INPUT
CURRENT
SERVICE
RECOMMENDED
1) 100 VAC ±10%, 47-63 Hz
12 A
rms
25
A
2) 110 VAC ±10%, 47-63 Hz
12 A
rms
25
A
3) 120 VAC ±10%, 47-63 Hz
11 A
rms
25
A
4) 200 VAC ±10%, 47-63 Hz
7 A
rms
15
A
5) 208 VAC ±10%, 47-63 Hz
7 A
rms
15
A
6) 220 VAC ±10%, 47-63 Hz
6 A
rms
15
A
7) 230 VAC ±10%, 47-63 Hz
6 A
rms
15
A
8) 240 VAC ±10%, 47-63 Hz
5 A
rms
15
A