LMX SERIES® OPERATION MANUAL
SECTION 4: Technical Specifications
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
Page 42 of 463
4.6
Protection Modes
PROTECTION
Protection Modes
Over Current fold-back or trip
Power fold-back or trip
Apparent Power fold-back or trip
Over Voltage trip
Over Temperature
OVP Range
0 - 105% Vmax
4.7
Metering
MEASUREMENTS
SPECIFICATION
AC Voltage (Vrms)
Range
0 – 340 VLN / 0-600 VLL
Resolution
0.01 V
Accuracy
± 0.1% F.S.
Frequency (Hz)
Fundamental Range
15 - 5000 Hz
Resolution
0.01 Hz
Accuracy
± 0.1% Rdg
AC Current (Arms)
Range
See Model Tables page 8 & 9
Resolution
0.01 Arms
Accuracy
15-45Hz, ± 0.25% of F.S.
45-500 Hz, ±0.1% F.S.
20-5,000 Hz, ± 0.5% F.S.
Current Crest Factor
Range
1.00 - 10.00
Resolution
0.01
Accuracy
± 2.0% F.S.
AC or DC Power (W)
Range
See Model Tables page 8 & 9
Resolution
Front panel & Browser: 1 W, Interfaces: 0.1 W
Accuracy
± 0.75 % F.S.
Apparent Power (VA)
Range
See Model Tables page 8 & 9
Resolution
Front panel & Browser: 1 VA, Interfaces: 0.1 VA
Accuracy
± 0.75 % F.S.
Power Factor
Range
0.00 - 1.00
Resolution
0.01
4.8
Other Measurements
Measurements
1
For currents > 1.0 Arms