LMX SERIES™ OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
Page 256 of 463
Query Format
[SOURce:]CURRent:LIMit#:MAXimum?
Description
This command returns the maximum available programmable current
limit setting. Note that the returned value is a function of the
“
SYSTem:COMPatible”
setting
UPC If UPC mode is enabled, this command always returns 2000.0000 to
emulate the UPC controllers
DISABLED With UPC mode disabled, this command returns the max. available
current output per phase. This value is a function of the LMX model
and the number of units that are connected in parallel.
Returned Data Format
<nr2>
Query Example
CURR:LIM:MAX?
41.6667
Query Format
[SOURce:]CURRent:LIMit#:DEFault?
Description
This command returns the default current limit setting at power up
for the referenced phase.
Returned Data Format
<nr2>
Query Example
CURR:LIM1:DEF?
41.67
Query Format
[SOURce:]CURRent:LIMit#:MINimum?
Description
This command returns the minimum current limit setting available for
the referenced phase.
Returned Data Format
<nr2>
Query Example
CURR:LIM:MIN1?
0.000
Command Syntax
[SOURce:]CURRent:PROTect:TOUT
Description
This command sets the programmable delay to hold off when the
current trip protection level is exceeded. If the load current remains
at or above this current level during this time period, the output will
turn off at the end of the time delay.
Note: This command serves the same purpose as the
“[SOURce:]PROTect”TDELAY” command and is provided for backward
compatibility with PPS UPC controllers.
Parameters
0 – 65535
Parameter Format
<nr1>
Example
CURR:PROT:TOUT 2
Query Format
[SOURce:]CURRent:PROTect:TOUT?
Returned Data Format
<nr1>
Query Example
CURR:PROT:TOUT?
2