LMX SERIES™ OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
Page 295 of 463
Query Syntax
[SOURce:]STEP:PHASe:DELTa#:MAXimum?
Description
This command returns the maximum permissible set value of the
delta STEP phase angle for selected phase #
Returned Data Format
<nr1>
Query Example
STEP:PHAS:DELT1:MAX?
Query return values for MINimim, MAXimum and DEFault are dependent on
MODE and interdependent parameter value settings
Query Syntax
[SOURce:]STEP:PHASe:DELTa#:DEF?
Description
This command returns the default set value of the delta STEP phase
angle for selected phase #
Returned Data Format
<nr1>
Query Example
Query return values for MINimim, MAXimum and DEFault are dependent on
MODE and interdependent parameter value settings
Command Syntax
[SOURce:]STEP <cr>
>>> Alias for PROGram:TRANsient command. <<<
Description
This command controls step transient execution
Parameters
< RUN | STOP | PAUSe | STEP | RESTart >
Parameter Format
<cr>
Example
STEP RUN
Query Format
[SOURce:]STEP?
Description
Query format returns the step transient execution state as either
RUN, STOP, PAUS, STEP or REST
Returned Data Format
<nr1>
Return values respresent running state as follows:
0
Stopped
1
Running
2
Paused
3
Stepping
4
Waiting for trigger
Query Example
STEP?
1