ADF SERIES™ OPERATION MANUAL
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
ADF Series Power Source Operation Manual
Page 111 of 349
6.7.3
RAMP TIME & SLEW RATE SETTINGS Screen
This screen allows programming of the update ramp time or individual voltage and
frequency slew rates, which are applied when changing output settings. Ramp time and
slew rate settings are mutually exclusive so Ramp time must be disabled in order to program
individual voltage, frequency and phase update rates. Setting a slew rate other than the
maximum value allows voltage and frequency changes to occur at a controlled rate of
change. The Ramp time when enabled applies to any setting change equally.
Figure 6-9: RAMP TIME & SLEW RATE SETTINGS Screen
The following parameters can be set from this screen:
Ramp time
Sets the time over which output changes will take place. For
the time set, output changes will ramp from their previous
set value to the new set value. When
DISABLED
, changes
will occur at the programmed slew rate settings in the SLEW
RATE SETTING screen, as both cannot be in effect at the
same time. Settings Slew Rate settings provide control over
individual parameters whereas the RAMP TIME setting
applies to all parameters (F, Vac, Vdc and Phase) changes
equally.
Voltage AC
AC Voltage slew rate in Vrms per msec. Available range is
0.01 Vrms/ms through 300 Vrms/ms.
Frequency
Frequency slew rate in Hz per msec. Available range is 0.01
Hz/ms through 1200 Hz/ms.
NOTE:
Programmed Slew Rate settings will only take effect when the RAMP TIME setting is
DISABLED
.
The soft keys on the SLEW RATE SETTINGS screen provide access to additional functionality
as listed in the table below.
SOFT KEY
Description
Apply All (SK1)
Applies all changes made (highlighted in grey) and returns to
previous screen.
Summary of Contents for 1150ADF
Page 348: ......