4.3.3
Option V - Extended AC Voltage Ranges – Supplemental specs
The ADF-2V / ADF-4V provides three extended voltage ranges, 0 through 2. The maximum
programmable Vrms AC limits for each of these extended ranges are:
•
Range 0
312V
LN
•
Range 1
320 V
LN
•
Range 2
333 V
LN
Range 0 is activated by setting the AC voltage user limit to a value between 300 and 312.
More details on extended range 0 are provided in section 6.4.11, page 97.
Range 1 and 2 must be enabled using a bus command before they can be activated in a
similar way. Refer to
Note:
For voltage limits higher than 312V L-N, this mode must be enabled first. See
“
[SOURce:]VOLTage:EXTend”
command in section 8.7.2 on page 199.
The following specification adjustments apply for each extended range mode.
Range 0: up to 312V
•
Standard THD specs apply only from 45-100Hz
•
Only supported in three phase mode
•
Maximum output power is 3kW per phase
Range 1: up to 320V
•
Max. current limited to 35Arms/phase
•
Limits maximum frequency set point to 800Hz
•
Does not guarantee THD specification but designed to have THD < 1.0% at
Pout<9kW
Range 2: up to 333V
•
Max. current limited to 35Arms/phase
•
Limits maximum frequency set point to 800Hz
•
Does not guarantee THD. Control loop may saturate at V > 320, giving a THD of 2-3%
at 333V/9kW